Autotransformer: 6 Essential Uses and Brilliant Savings

Share:
Electrical Machines
Autotransformer: 6 Essential Uses and Brilliant Savings

One winding, one core and a tap in the middle can do the job of a full transformer with far less copper. The price is that input and output are connected, so knowing where the trick works and where it is unsafe matters.

Single Winding Copper Saving Variac Starter Taps Grid ICT

An autotransformer uses one winding for both primary and secondary, so part of the power passes straight through by conduction. That makes it smaller, cheaper and more efficient, but it gives no electrical isolation.

Hello everyone, today we are going to learn how an autotransformer works, how much copper it saves, where it is used in starters, variacs and grid substations, and why it never gives isolation.
autotransformer

What Is an Autotransformer?

An autotransformer is a transformer with a single winding on one core, where a portion of that winding is common to both the input and the output circuits. It works on the same induction principle as any transformer, explained in Faraday law of electromagnetic induction, but it saves material because primary and secondary share turns.

In a step down autotransformer the supply is connected across the whole winding and the load is taken from a tap and one end. In a step up unit the supply goes to the tap and the load takes the full winding.

motor-starters-part-10-autotransformers
Image credit: EEPower. Diagram courtesy of EEPower, shown here for educational reference.

The voltage ratio still follows the turns ratio, just as in transformer turns ratio and secondary voltage. What changes is how the power travels from input to output.

Advertisement

How an Autotransformer Transfers Power

In a two winding transformer, every watt reaches the load through the magnetic core. In an autotransformer, part of the power flows straight from supply to load through the shared copper, and only the rest is transformed magnetically.

K = V low ÷ V high
Conducted power = S × K
Transformed power = S × (1 minus K)
Common winding current = I low minus I high

Example: 230 V to 180 V, load S = 2 kVA
K = 180 ÷ 230 = 0.783
I high = 2000 ÷ 230 = 8.70 A, I low = 2000 ÷ 180 = 11.11 A
Common winding current = 11.11 minus 8.70 = 2.42 A
Transformed power = 2 × (1 minus 0.783) = 0.43 kVA

This example shows the real advantage. Only 0.43 kVA of the 2 kVA load passes through the core, and the common section of the autotransformer carries just 2.42 A instead of 11.11 A, so it can be wound with much thinner wire.

The core and series section are sized for the transformed power, which is why an autotransformer is so compact when the two voltages are close. Rating rules for normal units are covered in transformer kVA rating calculation.

Do You Know?

When the voltage ratio is close to 1, almost all the power is conducted and very little is transformed. A 230 V to 220 V autotransformer handles about 96 percent of its load by direct conduction.

Copper Saving in an Autotransformer

For the same rating and voltage ratio, the copper needed by an autotransformer is (1 minus K) times the copper of a two winding transformer. The saving is therefore K times the copper of the two winding design.

Copper in autotransformer ÷ Copper in two winding = 1 minus K
Copper saving = K × Copper in two winding

K = 0.783: copper needed = 21.7 percent, saving = 78.3 percent
K = 0.5: copper needed = 50 percent, saving = 50 percent
K = 0.1: copper needed = 90 percent, saving = 10 percent

The table makes the rule clear: the closer the two voltages, the bigger the saving. For a ratio like 11 kV to 433 V, K is tiny, the saving disappears and an autotransformer would be both pointless and dangerous.

1 minus KCopper needed vs two winding
0.783K for 230 V to 180 V
78.3 %Copper saved at that ratio
2.42 ACommon winding current, 2 kVA example

Autotransformer Calculator

Voltage Ratio, Currents and Copper Saving
Result
K 0.783, copper saving 78.26 percent, I high 8.70 A, I low 11.11 A, common winding 2.42 A, transformed 0.43 kVA
Advertisement

Autotransformer vs Two Winding Transformer

FeatureAutotransformerTwo winding transformer
WindingsOne, with a tapSeparate primary and secondary
Electrical isolationNoneYes
Copper for same rating1 minus K timesFull amount
Size, losses and costLower when K is near 1Higher
Impedance and fault levelLower impedance, higher fault currentHigher impedance
Best ratio rangeClose voltagesAny ratio

The lower leakage impedance gives better regulation but lets more fault current through, so check the downstream breaker duty with a short circuit current calculation. Smaller copper and core also mean lower losses, a point you can test with transformer efficiency calculation.

Core losses still follow the usual split described in eddy current loss and hysteresis loss. An autotransformer simply needs less core for the same throughput power.

6 Essential Autotransformer Uses

Reduced Voltage Motor Starting
Taps of 50, 65 and 80 percent cut starting current from the line.
Variac for Testing
A sliding brush gives a smoothly variable output voltage.
Grid Interconnecting Transformer
Links 400 kV and 220 kV networks in substations.
Voltage Boosting on Long Feeders
Small boost or buck corrections at the end of a line.
Equipment Voltage Matching
Running 230 V machines on 110 V supplies and the reverse.
Audio and Electronics
Impedance matching and variable supply in labs.

The common thread in all six uses is a modest voltage change where isolation is not required. Wherever the ratio is large or user safety needs separation, an isolating transformer is chosen instead.

Autotransformer Starter for Induction Motors

An autotransformer starter feeds the motor through taps at reduced voltage, then switches it to full line voltage. EEPower describes taps generally set between 50 and 80 percent of line voltage, and notes that the starting current drawn from the supply falls with the square of the voltage ratio.

TapMotor voltageLine current, percent of DOLStarting torque, percent of DOL
80 %80 %64 %64 %
65 %65 %42 %42 %
50 %50 %25 %25 %

The Sprecher and Schuh reduced voltage starter catalogue lists exactly these figures for its autotransformer starters. Line current falls with the square because the motor current falls with voltage and the autotransformer itself steps that current down again.

Compared with star delta, the autotransformer starter offers a choice of taps and gives more torque per ampere of line current. The wider comparison is covered in motor starting methods compared and DOL vs star delta starter.

1
Start Contactor Closes
The star point contactor and start contactor connect the autotransformer at the chosen tap.
2
Motor Accelerates
The motor runs up on reduced voltage with reduced line current.
3
Star Point Opens
The star point opens and the winding acts as a series reactor.
4
Run Contactor Closes
Full voltage is applied without the motor being disconnected.
5
Autotransformer Drops Out
The start contactor opens and the transformer is out of circuit.

This five step sequence is the closed transition, or Korndorfer, method. Sprecher and Schuh lists its autotransformer starters as closed transition, which avoids the current and torque surge of an open changeover.

Quick Tip

Start with the 65 percent tap and move to 80 percent only if the motor stalls or the run up takes too long. Every step up in tap raises the line current and the voltage dip on the bus.

Second Worked Example: Tap Selection

A pump motor with 100 A full load current draws about 600 A when started direct on line. On the 65 percent tap the motor current becomes 0.65 × 600 = 390 A, and the line current becomes 0.65 × 390 = 253.5 A, about 42 percent of the direct online value.

The starting torque falls to the same 42 percent, so check that this exceeds the load torque at all speeds. Use motor full load current data and the motor starting voltage dip calculation to confirm the bus voltage stays acceptable.

Do You Know?

Schneider Electric lists a duty of fifteen 15 second starts per hour for NEMA sizes 2 to 5 in its reduced voltage starter catalogue. Frequent starting heats the autotransformer, so it is not meant for jogging duty.

Variac: The Variable Autotransformer

A variac is a toroidal autotransformer with a carbon brush that slides over bare turns on the winding. Moving the brush changes the tap point smoothly, so the output can be set anywhere from zero to slightly above the input voltage.

Laboratories and repair benches use it to bring up old equipment slowly, test relays at reduced voltage or check how a product behaves at low mains. Remember that a variac is still an autotransformer, so its output is never isolated from the mains.

Quick Tip

Always connect the variac neutral terminal to the supply neutral, never to the phase. A reversed connection leaves the output terminals at line potential even when the dial reads zero.

Grid Interconnecting Autotransformer

In Indian transmission substations, the interconnecting transformer that links the 400 kV and 220 kV systems is normally a three phase autotransformer bank. The ratio is close to 2, so a large share of power is conducted and the unit is much smaller than a two winding design, a benefit that helps in GIS and AIS substations alike.

Such units usually carry a delta tertiary winding to provide a path for third harmonic currents and stabilise the neutral. They also carry an on load tap changer for voltage control, and their connection follows the rules in transformer vector groups.

Step Down Autotransformer

Supply across full winding, load across part of it.

Best for: starters, voltage matching
Common
Step Up Autotransformer

Supply across part of winding, load across full winding.

Best for: feeder boosting
Booster
Variable Autotransformer

Sliding brush gives a continuous tap.

Best for: labs and test benches
Adjustable
Myth: An autotransformer is just a cheaper isolation transformer.
Fact: It gives no isolation at all, because input and output share one winding.
Myth: Copper saving is always large.
Fact: Saving equals K, so it is big only when the voltages are close.
Myth: A variac at zero volts is safe to touch.
Fact: The output is still tied to the supply, so it can sit at line potential.
Myth: Lower impedance is always better.
Fact: Lower impedance raises fault current, so breakers must be rated for it.
Advertisement

No Isolation: The Main Safety Risk

Because the output is part of the input winding, a fault that opens the common section puts nearly the full input voltage on the load. A step down autotransformer from 415 V can therefore expose low voltage equipment to the full supply.

The lack of separation also carries any earth fault or neutral shift straight through, so the earthing scheme must suit the TN, TT and IT earthing systems on both sides. Where people touch the output, choose real galvanic isolation instead.

Advantages of an Autotransformer
  • Less copper and core for the same rating.
  • Higher efficiency and lower losses.
  • Better voltage regulation.
  • Smaller size and lower cost.
Limitations and Risks
  • No electrical isolation between circuits.
  • Higher fault current from low impedance.
  • Savings vanish at large voltage ratios.
  • Open common winding exposes load to full voltage.

Autotransformer Inspection Checklist

  • Confirm the voltage ratio suits an autotransformer, ideally below about 2 to 1.
  • Check fault level and breaker rating on the output side.
  • Verify neutral and earth connections on both circuits.
  • Inspect variac brush and track for wear and arcing.
  • Check starter tap setting and timer against the motor run up time.
  • Record insulation resistance and winding resistance during maintenance.

Large grid units also go through the full set of transformer routine and type tests before energisation. Winding resistance on each tap and ratio tests confirm that the common and series sections are correct.

Reduced Voltage Starter Catalogue PDF

PDF
Sprecher and Schuh Reduced Voltage Starters
Autotransformer starter taps, line current and torque comparison

Autotransformer Power and Control Video

Autotransformer FAQ

What is an autotransformer?

It is a transformer with one winding on one core, where part of the winding is common to both circuits. The output is taken from a tap on that single winding.

Part of the power flows straight through the shared copper and only the rest is transformed magnetically. This makes the unit smaller and cheaper than a two winding design.

How much copper does an autotransformer save?

The copper needed is (1 minus K) times that of a two winding transformer, where K is the low to high voltage ratio. The saving is therefore K times the two winding copper.

For 230 V to 180 V, K is 0.783 and the saving is about 78 percent. For a ratio of 10 to 1 the saving is only about 10 percent.

Why does an autotransformer give no isolation?

The input and output circuits share the same winding, so they are electrically connected. Any fault or high voltage on the input side can reach the connected load directly.

If the common section of the winding opens, the load can see almost the full input voltage. Use an isolating transformer wherever people or sensitive circuits need separation.

What taps does an autotransformer starter use?

Typical taps are 50, 65 and 80 percent of line voltage. Sprecher and Schuh lists line current and torque of 25, 42 and 64 percent of direct online values.

The line current falls with the square of the tap ratio. Starting torque falls in the same proportion, so pick the lowest tap that still accelerates the load.

What is a variac?

A variac is a variable autotransformer built on a toroidal core with a sliding carbon brush. Moving the brush changes the output voltage smoothly from zero upward.

It is widely used on test benches and in laboratories. Its output is not isolated from the mains, so handle it with the same care as live wiring.

Why are grid ICTs built as autotransformers?

The 400 kV to 220 kV ratio is close to 2, so a large share of power can be conducted directly. The unit becomes smaller, lighter and more efficient than a two winding design.

Both networks are solidly earthed systems, so the lack of isolation is acceptable there. A delta tertiary winding is usually added to handle third harmonic currents.

When should an autotransformer not be used?

Avoid it when the voltage ratio is large, because the copper saving almost disappears. Avoid it too wherever user safety depends on proper isolation from the supply.

Examples include control circuits handled by operators, medical equipment and portable tool supplies on construction sites. In those places a proper double wound isolating transformer is the correct choice.

Advertisement

Related Articles

External References

What We Learn Today

  • An autotransformer uses one tapped winding for both circuits, so part of the power is conducted directly and only the rest is transformed magnetically.
  • Copper needed is (1 minus K) times a two winding unit, so a 230 V to 180 V design saves about 78 percent copper.
  • Starter taps of 50, 65 and 80 percent give line current and torque of 25, 42 and 64 percent, but there is never isolation.
I hope you like above blog. There is no cost associated in sharing the article in your social media. Thanks for reading!! Happy Learning!!
Author · instrumentationblog.in
Editorial Staff
Instrumentation Blog’s Editorial Staff are industry professionals and technical writers with a strong interest in industrial electrical systems. They specialize in simplifying complex technical concepts into clear, practical, and easy to understand insights. All articles written by the Editorial Staff are technically reviewed before publication.
Technically reviewed on

Leave a Reply

Your email address will not be published. Required fields are marked *