Motor Starting Voltage Dip: 5 Easy Steps to Calculate It

Share:
Electrical Design & Calculations
Motor Starting Voltage Dip: 5 Easy Steps to Calculate It

A large motor started direct on line pulls several times its running current, and every other load on the bus feels the sag.

Locked Rotor kVA Transformer Impedance Contactor Dropout Starting Methods

When an induction motor starts, it draws a high, low power factor current until it reaches speed. That current flows through the source impedance and pulls down the bus voltage for seconds.

Hello everyone, today we are going to learn how to calculate the motor starting voltage dip, what limits keep contactors and drives running, and which starting methods reduce the sag.
motor starting voltage dip

Why a Voltage Dip Happens at Start

The motor starting voltage dip is the temporary fall in bus voltage while a large motor accelerates. Voltage Disturbance notes that a direct on line start draws 5 to 10 times full load current at a power factor of only about 10 to 30 percent, so the drop across transformer and cable reactance is large.

The dip lasts until the rotor reaches speed and current falls to its running value. Our induction motor guide explains why rotor current is so high at standstill.

Simplified model of a starting induction motor fed through source impedance
Image credit: Voltage Disturbance

Lights dim, contactors chatter and drives may trip on undervoltage. In weak systems the motor itself may fail to accelerate.

The same physics appears in any voltage sag event, but motor starts are predictable and can be calculated in advance.

Acceptable Dip Limits

ItemTypical LimitReason
Motor terminals during startAbout 80 percent of ratedEnough torque to accelerate
AC control devices85 percent to pick upContactors and relays must close
Contactor dropout60 to 70 percentBelow this, running loads drop out
Other buses, occasional startDip of 10 to 15 percentAvoid visible disturbance
Frequent startsDip of 3 to 5 percentFlicker limits

The CED Engineering course recommends about 80 percent terminal voltage during starting. It also notes that AC control devices need 85 percent of rated voltage to pick up.

Sites with sensitive electronics often set tighter limits. Check the utility rules at the point of common coupling as well.

5 Easy Steps to Calculate the Dip

1
Motor Rated kVA
kW ÷ (efficiency × power factor).
2
Starting kVA
Rated kVA × locked rotor current multiple.
3
Source Short Circuit kVA
Transformer kVA ÷ per unit impedance.
4
Dip Percent
Starting kVA ÷ (starting kVA + source kVA) × 100.
5
Compare
Check against the limits above and add cable drop.

Motor full load current and locked rotor multiple come from the nameplate or code letter, see motor full load current. Source strength links to the short circuit fault current.

This simple method assumes an infinite upstream grid and ignores preload. It is accurate enough for screening, and detailed studies use software.

Worked Example

Dip percent = kVA start ÷ (kVA start + kVA sc) × 100

Transformer 1000 kVA, impedance 6 percent
kVA sc = 1000 ÷ 0.06 = 16667 kVA
Motor 150 kW, efficiency × PF = 0.82, LRC = 6 × FLC
Rated kVA = 150 ÷ 0.82 = 183 kVA
kVA start = 6 × 183 = 1098 kVA
Dip = 1098 ÷ 17765 × 100 ≈ 6.2 percent at the transformer bus

Add the cable drop between the bus and motor terminals, calculated with starting current and a low power factor. Use the voltage drop calculation method with the locked rotor current.

On a generator, use its subtransient reactance instead of transformer impedance. The dip is usually much larger, which is why generator sizing depends on the biggest motor.

Starting Methods That Reduce the Dip

Star Delta

Line current falls to about one third during start.

Best for: pumps and fans with light starting torque
Low Cost
Autotransformer

Tapped voltage, adjustable starting current.

Best for: large motors on weak supplies
Flexible
Soft Starter

Thyristors ramp voltage smoothly.

Best for: conveyors and compressors
Smooth
VFD

Starts near rated current with full torque.

Best for: process loads needing speed control
Lowest Dip

Compare these options in motor starting methods compared and DOL vs star delta. Reduced voltage methods also reduce starting torque, so check the load can still accelerate.

A VFD gives the smallest motor starting voltage dip, since current stays near rated from zero speed.

Other Ways to Strengthen the Bus

Larger Transformer
Raises short circuit kVA.
Lower Impedance
Choose a transformer with lower Z percent.
Dedicated Feeder
Separate the motor from sensitive loads.
Larger Cables
Reduce drop at starting current.
Tap Adjustment
Raise bus voltage slightly.
Stagger Starts
Never start two large motors together.

Cable sizing for motors must consider both running current and starting drop, as shown in cable sizing for motor feeders.

Voltage Dip Calculator

Transformer Bus Dip at Start
Result
Starting 1098 kVA, dip 6.2 percent, bus at 93.8 percent

Try a 500 kW motor on the same transformer to see the dip pass 15 percent. That is the point where a soft starter or VFD becomes worth the cost.

Good Design Habits
  • Calculate dips before buying motors.
  • Check both bus and terminal voltage.
  • Include cable drop at starting current.
  • Use reduced voltage starters where needed.
Common Oversights
  • Ignoring generator reactance.
  • Starting several motors together.
  • Forgetting contactor dropout levels.
  • Using running PF for starting drop.

CED Motor Starting Analysis PDF

PDF
Introduction to Motor Starting Analysis
CED Engineering course by Velimir Lackovic

Voltage Drop at Start Video

Motor Starting Voltage Dip FAQ

What causes a motor starting voltage dip?
High, low power factor starting current flowing through source impedance.
What terminal voltage is needed during start?
About 80 percent of rated.
At what voltage do contactors drop out?
Around 60 to 70 percent.
How is the dip estimated?
Starting kVA divided by starting kVA plus source short circuit kVA.
Which starter gives the lowest dip?
A VFD.
Why is the dip worse on generators?
Generator reactance is much higher than a transformer.
How can the bus be made stronger?
Larger or lower impedance transformers and dedicated feeders.

Related Articles

External References

What We Learn Today

  • Starting current at low PF pulls down bus voltage.
  • Dip percent equals starting kVA over starting plus source kVA.
  • Reduced voltage starters and stronger sources keep dips within limits.
I hope you like above blog. There is no cost associated in sharing the article in your social media. Thanks for reading!! Happy Learning!!

Leave a Reply

Your email address will not be published. Required fields are marked *