ToggleOne undersized 24 V supply can reset a PLC every time a group of coils switches on. Here you add up every load, apply margin and temperature derating, plan redundancy and check the voltage that actually reaches the field.
Work out the current rating of a 24 V DC supply from the real load list of a PLC or instrument panel. The calculator adds margin and temperature derating, and the solved example shows each step with numbers.

What is 24VDC power supply sizing and how do you calculate the rating?
24VDC power supply sizing means adding the steady current of every load on the 24 V bus, adding a 20 to 25 percent margin and correcting for panel temperature. Rating = (sum of loads × 1.25) ÷ derating factor. Example: a 6.65 A load needs 8.31 A with margin, and at 65 °C (factor 0.875) the supply must give 9.50 A, so you pick a 10 A unit.
What Is 24VDC Power Supply Sizing?
24VDC power supply sizing is the job of choosing a DC supply whose rated current covers every load on the 24 V bus, plus margin, at the hottest temperature inside the panel. You size on current, then check inrush, redundancy and the voltage left at the far end of each field cable.
- IEC 61131 part 2 gives 20.4 to 28.8 V as the operating range for 24 V DC PLC supplies.
- Allow 22 mA for every 4 to 20 mA loop, because a failed transmitter can drive its signal above 21 mA.
- Eaton adds 20 percent to the calculated nominal load for longer supply life.
- Phoenix Contact QUINT units derate output by 2.5 percent per kelvin above 60 °C.
For the background on this voltage, read why PLC systems use 24 volts.
Eaton sizes a supply on two separate totals: the surge current of all loads and their sealed, steady current. A supply can pass the steady test and still fail when every coil pulls in at the same moment.
How Do You Calculate 24V Power Supply Load?
You calculate the 24 V load by listing every device on the supply, taking its maximum current from the datasheet and adding the currents together. Where a datasheet gives watts, divide by 24 to get amps.
| Load (example panel) | Qty | Current each | Total |
|---|---|---|---|
| PLC CPU and IO modules | 1 set | 2.5 A | 2.50 A |
| Two wire transmitters | 24 | 22 mA | 0.53 A |
| Solenoid valve coils | 8 | 0.35 A | 2.80 A |
| Interface relays | 16 | 0.02 A | 0.32 A |
| HMI, switch and lamps | 1 lot | 0.5 A | 0.50 A |
| Steady load | 6.65 A (159.6 W) |
The currents in this table are example values, so take the real ones from each datasheet. Module current for a rack is usually listed in the PLC power budget, as covered in IO modules in industrial automation.
A two wire transmitter draws its loop current from the panel supply, so 24 loops at 22 mA add about half an amp. In this example the solenoids are the largest block; the solenoid valve working principle covers how the coil works.
Fit suppression diodes on relay coils as shown in relay coil suppression, so turn off spikes stay off the 24 V bus.
Count only loads that can be on together, and write that assumption on the load list. If the sequence can energise every solenoid at once, size for all of them.
24VDC Power Supply Sizing Formula and Calculator
In 24VDC power supply sizing, the rating you need is the steady load plus margin, divided by the temperature derating factor. The calculator uses the Phoenix Contact QUINT figure of 2.5 percent per kelvin above 60 °C and picks the next standard size.
With margin = I × (1 + margin ÷ 100)
Derating factor = 1 minus 0.025 × (T minus 60), for T above 60 °C
Required rating = I with margin ÷ derating factor
Solved example: the panel in the load table runs at 65 °C inside, and we want 25 percent margin. Here are the same numbers the calculator uses by default.
With margin = 6.648 × 1.25 = 8.31 A
Derating factor = 1 minus 0.025 × 5 = 0.875
Required = 8.31 ÷ 0.875 = 9.50 A
Choose a 10 A, 240 W supply
At 50 °C the same panel would need only 8.31 A. For the transmitter side of the same panel, check each loop with our HART loop voltage budget calculator.
How Much Margin Should a 24V Power Supply Have?
Keep 20 to 25 percent margin over the calculated steady load. Eaton uses 20 percent for extended life, and the RSP Supply sizing guide warns against picking a supply whose rating only equals the total load.
Margin also covers loops added during commissioning, and a cooler supply ages more slowly, as covered in power supply aging in automation.
- Covers spare IO and later devices
- Supply runs cooler and lasts longer
- Short overloads stay in boost range
- None: supply trips on start up
- Too much: cost, heat and rail space
- Added twice by two engineers
Why Does Inrush Current Trip a 24V Supply?
Inrush trips a supply when the surge of many loads starting together is higher than the short time current the supply can deliver. Coils, PLC module input capacitors and HMI start up all add to it.
Eaton sums the inrush of each coil and checks the total against the supply surge rating, which for its PSG range is a 1 second surge at 10 second intervals.
The Phoenix Contact QUINT4 40 A datasheet gives a static boost of 45 A, a dynamic boost of 60 A for 5 seconds and 215 A for 15 ms to trip a branch fuse. Size the branch protection with the fuse selection guide and MCB rating method, so that a shorted field cable opens its own fuse.
The QUINT4 datasheet says its 215 A fuse breaking pulse is about 6 times nominal current. It is meant to blow a small branch fuse quickly.
How Does Ambient Temperature Derate a Power Supply?
Above a stated temperature, the supply must deliver less current to stay inside its limits. For Phoenix Contact QUINT supplies and their redundancy modules, output falls by 2.5 percent per kelvin above 60 °C, up to 70 °C.

Use the air temperature near the supply, which is often higher than the room. Estimate it with the panel heat load calculation, since the losses of the supply itself are part of that heat.
Put the supply low in the panel, away from drives and braking resistors. The ambient you enter in the calculator should be the hottest summer value, not the commissioning day reading.
How to Build a Redundant 24 V Supply With Diode or ORing Modules
For redundancy you run two supplies in parallel through a diode or MOSFET ORing module, and each supply must carry the whole load alone. Phoenix Contact states this rule in the QUINT DIODE datasheet, so that if one unit fails the other takes over without a break.
QUINT DIODE drops 0.5 V and loses up to 10 W at 20 A.
QUINT ORING drops 0.2 V at 40 A with up to 8 W loss.
One supply for system loads, another for solenoids.
The diode drop comes off the bus, so set the supply output a little higher; the QUINT4 adjusts from 24 to 29.5 V. See Schottky diode limitations and full layouts in redundant power supply for PLC.
For ride through on mains failure, finish 24VDC power supply sizing first and then size the battery with battery backup time calculation.
How Do You Check Voltage Drop to Field Instruments?
Multiply the loop length by two, by the current and by the cable resistance per metre, and subtract the result from the supply voltage. The device at the far end must still see a voltage above its minimum supply rating.
L = one way length (m), R = ohm per km
Example: 2 × 200 × 0.35 × 12.1 ÷ 1000 = 1.69 V
Coil voltage = 24.0 minus 1.69 = 22.3 V
The 12.1 ohm per km figure is the IEC 60228 maximum for 1.5 mm² copper at 20 °C, and hot cable has a higher resistance. Pick the core size with cable size for load current, or work it out online with this cable voltage drop calculator.
Transmitter loops share voltage between cable, the PLC analog input resistor and the transmitter. See cable sizing basics for how resistance grows with length.
| Field symptom | Likely cause | What to check |
|---|---|---|
| CPU resets when coils switch on | Supply too small for inrush | Surge total vs boost rating |
| Far solenoid drops out | Cable voltage drop | Coil voltage under load |
| Supply trips on hot days | No temperature derating | Panel ambient |
| One redundant unit takes all load | Unequal output settings | Set both outputs equal |
Measure the voltage at the device terminals with the load running. A reading taken at the supply terminals hides the cable drop.
24VDC Power Supply Sizing Checklist
Run through this checklist before you freeze the supply on the panel drawing.
- Every 24 V load listed with its datasheet current
- Transmitters counted at 22 mA each
- Margin of 20 to 25 percent added once
- Derating applied for the hottest panel ambient
- Each redundant supply sized for the full load
- Voltage at the farthest device checked under load
Keep system power and field power on separate fused branches, as shown in PLC wiring from field instrument to system cabinet and marshalling cabinet wiring. A short in one field cable then stays in its own branch.
The RSP Supply video below walks through a load list with a PLC, a radio and a network switch.
In that example the loads total 100 W, and a 5 A supply at 24 V gives about 120 W. Our calculator follows the same sum and adds the margin and derating steps.
24VDC Power Supply Sizing FAQ
24VDC power supply sizing is selecting a DC supply whose current rating covers all panel and field loads with margin. For a 6.65 A load with 25 percent margin you need at least 8.31 A, before any derating for temperature.
List every load, add the currents, multiply by 1.25 and divide by the derating factor. A 6.65 A load at 65 °C gives 6.65 × 1.25 ÷ 0.875 = 9.50 A.
Then choose the next standard size, here 10 A.
A failed transmitter can drive its signal above 21 mA under NAMUR NE43, so 20 mA is too low for sizing. Counting 22 mA per loop covers that alarm current with a little room, and 24 loops then add 0.53 A to the panel load.
Steady load is the current loads draw once running, while inrush is the short surge at switch on. Eaton sums both separately for every coil, and the supply surge rating must cover the inrush total even when the steady load fits easily.
Above 60 °C, Phoenix Contact QUINT supplies lose 2.5 percent of output per kelvin. At 65 °C the factor is 0.875, so an 8.31 A requirement grows to 9.50 A, and a supply sized at room temperature can trip on a hot day.
The usual mistake is sharing the load across two units so that neither can carry it alone. Phoenix Contact states that each redundant supply must handle the full load, so a 10 A load needs two 10 A supplies and a suitable diode or ORing module.
Choose a size where the drop at full coil current leaves the device above its minimum voltage. A 0.35 A coil at 200 m on 1.5 mm² copper drops 1.69 V, so longer runs or bigger coils may need 2.5 mm² cable.
Related Articles
- 24 Volts in PLC Systems
- Redundant Power Supply for PLC
- Power Supply Aging in Automation
- Panel Heat Load Calculation
- Fuse Selection Guide
External References
- Phoenix Contact QUINT DIODE Redundancy Module Data Sheet (PDF)
- Eaton: How to size a power supply
- Wikipedia: Switched mode power supply
What We Learn Today
- 24VDC power supply sizing starts with a full load list, counting PLC modules, transmitters at 22 mA, solenoid coils, relays and every other panel load.
- Add 20 to 25 percent margin, then divide by the derating factor, which falls by 2.5 percent per kelvin above 60 °C for QUINT supplies.
- Each redundant supply must carry the full load alone, and the voltage at the farthest field device must be checked with the load running.