Panel Heat Load Calculation: Fan Formula & Calculator

Share:
Design
Panel Heat Load Calculation: Heat Sources, IEC 60890 Surface Area Method, Fan Airflow Formula, Cooling Unit Sizing and a Solved Example

Every watt that a drive, power supply or PLC loses ends up as heat inside your control panel. This article shows how to add up those losses, how much the enclosure skin removes and how big the fan or cooling unit must be.

Heat Sources IEC 60890 Area Fan Airflow m³/h Cooling Unit Sizing Calculator

A panel heat load calculation tells you how many watts must leave the enclosure to keep the electronics inside at a safe temperature. We cover the loss of each device, the surface area method, the fan formula and a solved example.

Hello everyone, today we are going to learn panel heat load calculation step by step, from listing the heat sources to choosing the right fan or cooling unit for an industrial enclosure.
panel heat load calculation

What Is Panel Heat Load Calculation?

Panel heat load calculation is the method of adding up the power lost as heat by every device inside an enclosure and comparing it with the heat the enclosure can shed to the surrounding air. The difference decides whether natural cooling is enough or a fan, heat exchanger or cooling unit is required.

Quick Answer
  • Internal heat Qv = sum of losses of VFDs, power supplies, PLC, relays and transformers
  • Surface heat Qs = A × k × ΔT, with k = 5.5 W/m²K for painted sheet steel
  • Fan airflow V = f × (Qv minus Qs) ÷ ΔT in m³/h, with f = 3.1 near sea level
  • If ambient is hotter than the set point, size a cooling unit for Qv plus the heat gain through the walls

The input power of a device is not its heat load, only the part that is lost is. A 22 kW drive does not put 22 kW of heat into the panel, it puts only its own losses, and this simple point is the base of every correct panel heat load calculation.

Cabinet cooler family for electrical enclosure cooling
Image credit: EXAIR. Photo courtesy of EXAIR, shown here for educational reference.
Do You Know?

EXAIR states that most electrical components are designed to operate at about 35 °C. Many plant rooms in India cross that value for several months, so a fan alone is often not enough there.

Advertisement

How to Calculate Heat Load of Control Panel Components

The first job is a device list with the power loss of each item, taken from the datasheet. Manufacturers usually give this as power loss, heat dissipation or watt loss, and the value at full load is the one to use.

Variable Frequency Drives

Usually the biggest source. Pfannenberg estimates that about 3 % of the drive energy becomes heat, roughly 22 W per HP.

Best for: Main motor control panels
Largest
Switch Mode Power Supplies

Loss = output power × (1 ÷ η minus 1). A 240 W unit at 90 % efficiency loses about 27 W.

Best for: 24 V DC control circuits
Medium
PLC, I/O and Communication

CPU, I/O cards, switches and gateways each lose a few watts. Use the module datasheet values.

Best for: Automation panels
Small
Transformers and Chokes

Control transformers and line reactors lose iron and copper loss continuously.

Best for: Panels with 415 V to 230 V supply
Medium
Contactors, Relays and MCBs

Coils and contact resistance add a few watts each, which adds up in large panels.

Best for: MCC and relay panels
Small
Power supply loss = Pout × (1 ÷ η minus 1)
240 W × (1 ÷ 0.90 minus 1)
≈ 26.7 W
VFD loss ≈ 3 % of rated power

AutomationDirect gives the example of its GS3 2020 AC drive, which has a watt loss of 750 W, or about 2,559 BTU/hr. Always prefer such a published value over a thumb rule when you do a panel heat load calculation, and read our VFD sizing and selection guide to know which drive rating you actually have.

Switch mode supplies also age, and their efficiency drops as capacitors dry out, as explained in power supply aging in automation. If you use two supplies with a diode module, as in a redundant power supply for PLC, count the losses of both supplies and the module.

Quick Tip

Add 10 to 20 % margin to the device total for future I/O, extra relays and the heat of cable ducts. It is far cheaper than replacing a fan with a cooling unit after commissioning.

Panel Heat Load Calculation Formula With the Surface Area Method

The enclosure walls themselves move heat to the outside air when the inside is warmer. Rittal writes this as Qs = A × k × ΔT, where A is the effective surface area per IEC 60890 and k is the heat transfer coefficient.

Qs = A × k × ΔT
A = effective area in m²
k = 5.5 W/m²K (painted sheet steel)
ΔT = Ti minus Tu in K

IEC 60890 does not count all six faces equally, because a face against a wall or the floor sheds little heat. For a single enclosure standing free on all sides, the effective area is shown below, with W, H and D in metres.

InstallationEffective area A (m²)
Single, free standing1.8 × H × (W + D) + 1.4 × W × D
Single, wall mounted1.4 × W × (H + D) + 1.8 × D × H

The heat transfer coefficient depends on the material. AutomationDirect lists 5.5 W/m²K for painted steel, 3.7 for stainless steel, 12 for aluminium and 3.5 for plastic or insulated stainless steel.

The degree of protection does not change k, but a sealed IP rating like IP 55 or IP 66 rules out simple louvres.

How to Calculate Fan Airflow for Control Panel Cooling

When the walls cannot remove all the heat and the ambient air is cooler than the set point, a filter fan pushes cool air through. Rittal gives the required volume flow as V = f × Qv ÷ ΔT, where f is an altitude factor.

V = f × (Qv minus Qs) ÷ ΔT
V in m³/h, Q in W, ΔT in K
f = 3.1 m³K/Wh at 0 to 100 m
Altitude above sea levelFactor f (m³K/Wh)
0 to 100 m3.1
100 to 250 m3.2
250 to 500 m3.3
500 to 750 m3.4
750 to 1000 m3.5

Thin air carries less heat, so a panel in Pune at about 560 m needs f = 3.4, nearly 10 % more air than the same panel in Mumbai. In imperial units, Pfannenberg uses CFM = 1.82 × W ÷ ΔT in °C, and AutomationDirect uses 3.17 × W ÷ ΔT in °F.

Filters create back pressure, so check fan curves as shown in electronic cooling fans and thermal efficiency.

Do You Know?

Pfannenberg gives a quick rule of about 4 CFM per HP of drive to hold the enclosure 10 °C above ambient. It is a useful sanity check, but it never replaces a proper heat balance.

Solved Example of Panel Heat Load Calculation

Take a free standing painted steel panel 0.8 m wide, 2.0 m high and 0.6 m deep with 600 W of internal losses. The maximum inside temperature is 40 °C, the plant room ambient is 30 °C and the site is near sea level.

A = 1.8 × 2.0 × (0.8 + 0.6) + 1.4 × 0.8 × 0.6
A = 5.04 + 0.672 = 5.712 m²
Qs = 5.712 × 5.5 × 10 = 314.2 W
Net heat = 600 minus 314.2 = 285.8 W
V = 3.1 × 285.8 ÷ 10 ≈ 88.6 m³/h

The answer is a fan delivering about 89 m³/h at the real working point, so a catalogue fan of roughly 120 to 150 m³/h free flow is a safe pick. If the ambient rises to 45 °C, the fan can no longer help and a cooling unit is required.

Panel Heat Load and Fan Airflow Calculator (free standing steel panel)
Result
Area 5.71 m², surface loss 314 W, net heat 286 W, fan airflow 88.6 m³/h
Advertisement

Control Panel Cooling Methods Compared

Once the panel heat load calculation gives you a number, the next choice depends on two facts: is ambient air cooler than the set point, and can dusty or humid outside air enter the panel. The AutomationDirect white paper sorts the options into convection and closed loop methods.

Natural convection
Louvres or vents only. Works for small loads when ambient is well below the set point.
Filter fan
Open loop forced air. Cheap and low power, but lets in dust and humidity.
Air to air heat exchanger
Closed loop, keeps the enclosure rating. Needs ambient cooler than inside.
Cooling unit
Refrigeration circuit that can hold the inside below ambient. Size in watts or BTU/hr.
Vortex cooler
Runs on compressed air with no electricity, for hazardous or dirty areas.
Filter fan
  • Lowest cost and power draw
  • Simple sizing with one formula
  • Easy to replace in the field
  • Works well in air conditioned control rooms
Cooling unit
  • Higher cost and needs a drain
  • Draws much more power than a fan
  • Must be sized for wall heat gain too
  • Can create condensation if set too low

For a cooling unit, add the heat flowing in through the walls: Qcool = Qv + A × k × (Tu minus Ti). Multiply watts by 3.413 to get BTU/hr, the unit used in many Indian catalogues, and compare it with how room units are rated in what is an HVAC system.

Quick Tip

Set a cooling unit to about 35 °C, not 20 °C. A cold panel in a humid plant pulls moisture out of the air, and water on terminals is worse than a few extra degrees, a risk similar to the one in dew point in instrument air.

Step by Step Procedure

1
List devices
Write every heat producing device with its datasheet power loss.
2
Add losses
Sum the losses and add 10 to 20 % margin for future additions.
3
Find area
Use the IEC 60890 formula for your mounting and measure W, H and D.
4
Set ΔT
Choose the maximum inside temperature and the worst ambient of the site.
5
Surface loss
Calculate Qs = A × k × ΔT and subtract it from the internal heat.
6
Select cooling
Fan if ambient is lower, cooling unit if ambient is higher or the room is dirty.
Myth: The heat load is the total input power of the panel.
Fact: Only the lost power becomes heat. Use the loss figure, which for drives is a few percent of rating.
Myth: A bigger fan always cools the panel better.
Fact: If ambient is above the set point, more air only brings in more heat. A cooling unit is the only answer then.
Myth: A sealed IP 66 panel does not need a heat check.
Fact: A sealed panel relies only on its skin and a closed loop device, so the calculation matters even more.
Advertisement

Field Troubleshooting for Hot Panels

Many hot panels suffer from blocked filters or a dead fan, not a wrong panel heat load calculation. A quick thermal scan, as shown in infrared thermography of electrical panels, locates the hot spot in minutes.

SymptomLikely causeFix
Drive trips on heat sink over temperatureClogged filter matClean or replace the mat on a fixed schedule
Top of panel much hotter than bottomFan and exhaust at the same levelFan low, exhaust grille high
Water drops inside panelCooling unit set too coldRaise set point to about 35 °C
Hot even with a big fanAmbient above the set pointChange to a cooling unit or heat exchanger
One terminal very hotLoose connection, not panel loadRetighten and check with a thermal camera
  • Datasheet losses for every drive, supply and PLC module
  • Mounting type chosen for the IEC 60890 area
  • Worst summer ambient used, not the average
  • Altitude factor f taken from the site height
  • Fan flow checked at the working point, not free flow

Heat also hurts protection devices, because a hot panel shifts the trip point of a thermal overload relay. In power panels, see how heat is handled in a PCC panel with large busbars.

For single hot components, a local heat sink sized with our heat sink calculation tool can move heat to the fan airflow. The basic physics of conduction through walls is covered in what is thermal conductivity.

The capacitor lifetime calculator shows in numbers why a cooler panel lasts longer. Good cooling pays back in fewer power supply failures.

PDF
How to Select and Size Enclosure Thermal Management (AutomationDirect)
White paper with fan, cooling unit, heater formulas and k values

Panel Heat Load Calculation FAQ

How do you calculate the heat load of a control panel?

Add the power loss of every device inside the panel, taken from datasheets, and include a margin for future items. Then subtract the heat that the enclosure surface can shed, found with the formula A × k × ΔT for the walls.

What remains is the net heat that a fan, heat exchanger or cooling unit must remove. This is the core of every panel heat load calculation you will do.

How much heat does a VFD produce?

Pfannenberg estimates that about 3 % of the energy passing through a drive becomes heat, which is close to 22 watts for every horsepower. A 100 HP drive therefore adds roughly 2.2 kW of heat to the panel.

The exact figure is printed in the drive manual as power loss or watt loss. Always use that datasheet number when it is available, because losses vary with switching frequency and load.

What is the formula for fan airflow in an electrical enclosure?

Rittal gives the airflow as V = f × Q ÷ ΔT, with V in cubic metres per hour, Q in watts and ΔT in kelvin. The factor f is 3.1 near sea level and rises with altitude.

Use the net heat after subtracting the surface loss as the heat value. Then pick a fan whose real airflow with filters fitted still meets the calculated value at the working point.

When do you need a cooling unit instead of a fan?

A fan can only cool when the ambient air is colder than the maximum allowed inside temperature. When the ambient is equal or hotter, a fan only pushes more heat into the enclosure.

In that case a cooling unit must remove the internal losses plus the heat that leaks in through the walls. Dirty or oily areas also favour closed loop cooling to keep the electronics clean.

What temperature should a control panel be kept at?

EXAIR notes that most electrical components are designed to work at about 35 °C, and the electrical industry rule says life halves for every 10 °C rise above the rating. Many designers therefore target 35 to 40 °C inside.

Check the lowest rated device in the panel, often a drive or power supply, and set the limit from it. Avoid cooling far below ambient, since that can cause condensation on cold surfaces.

Advertisement

Related Articles

External References

What We Learn Today

  • A panel heat load calculation adds the datasheet losses of drives, power supplies and PLC modules, never their input power, plus a margin.
  • The enclosure surface sheds Qs = A × k × ΔT, where A follows IEC 60890 mounting rules and k is 5.5 W/m²K for painted steel.
  • Fan airflow is V = f × net heat ÷ ΔT in m³/h, while a hotter ambient than the set point calls for a cooling unit.
I hope you like above blog. There is no cost associated in sharing the article in your social media. Thanks for reading!! Happy Learning!!
Sunayana Gadepatil, author at Instrumentation Blog
Author · instrumentationblog.in
Ms. Sunayana Gadepatil is an instrumentation professional, technical writer, and the author behind Instrumentation Blog. With a strong interest in industrial instrumentation, process measurement, and automation, she specializes in simplifying complex technical concepts into clear, practical, and easy to understand insights. Through her articles, Ms. Sunayana shares valuable knowledge on flow, pressure, level, temperature, control systems, and industrial automation for engineers, students, technicians, and industry professionals.
Technically reviewed on

Leave a Reply

Your email address will not be published. Required fields are marked *