ToggleAccuracy, hysteresis and drift tell you how good a reading is once the process settles. Time constant, lag and dynamic error tell you how far the reading trails behind when the process moves fast.
Every instrument datasheet mixes steady state terms like accuracy and linearity with time based terms like response time. Below we separate the two groups, work out a first order step response and test both on a calibration bench.

What are static and dynamic characteristics of an instrument?
Static and dynamic characteristics describe how an instrument behaves with a steady input and with a changing input. Static terms include accuracy, precision, sensitivity, resolution, linearity, hysteresis, dead zone, drift, range and span. Dynamic terms include speed of response, lag, fidelity, dynamic error and time constant. For example, a first order sensor with τ = 8 s reaches 63.2% of a step change after 8 s and about 99.3% after 40 s.
What Are Static and Dynamic Characteristics of Instruments?
The static and dynamic characteristics of an instrument are the two sets of performance terms that tell you how well it measures. Static terms apply when the input is steady, and dynamic terms apply when the input is changing with time.
- Static terms come from point by point calibration against a reference.
- Dynamic terms come from a step, ramp or sine input watched over time.
- A first order sensor reaches 63.2% of a step at one time constant, 95% at three and over 99.3% at five.
A transmitter that is accurate on the bench can still read late in a fast loop, so you need to check static and dynamic characteristics together. Read common calibration terms first if as found and as left are new to you.
What Are the Static Characteristics of Measuring Instruments?
Static characteristics describe the relation between input and output once the reading has fully settled. We check them at fixed points across the range, so time is not part of the test.
Closeness of the reading to the true value, as a percent of span or reading.
Agreement between repeated readings of the same input.
Output change divided by input change, such as 1.6 mA per bar.
Smallest input change that gives a visible output change.
Largest deviation of the curve from a straight line, in percent of span.
Output difference at one input approached rising, then falling.
Largest input change that gives no output change, also called dead band.
Slow output change at constant input, as zero drift or span drift.
Range is 0 to 10 bar for example; span is the difference, 10 bar.
Accuracy and precision are often confused, so keep the target shooting picture of accuracy versus precision in mind. A gauge can repeat to 0.1% and still read 2% high; that gauge is precise but not accurate.
In digital systems the ADC bit count sets the resolution, the smallest step you can see. Our note on PLC analog input resolution shows how 12 bit and 16 bit cards differ.
Span = 10 minus 0 = 10 bar
Sensitivity = 16 mA ÷ 10 bar = 1.6 mA/bar
At 5 bar: rising 12.02 mA, falling 12.10 mA
Hysteresis = 0.08 ÷ 16 × 100 = 0.5% of span
You can repeat the error part with our calibration error calculator and compare it with the datasheet limit.
The ISA automation dictionary notes that dead band is expressed as a percent of span and causes phase lag between input and output. So a static fault also hurts loop dynamics.
What Are the Dynamic Characteristics of an Instrument?
Dynamic characteristics describe how the output follows an input that changes with time. They tell you how fast the instrument responds and how much error it shows while the process is moving.
Tutorialspoint lists speed of response, dynamic error, fidelity and lag as the four main dynamic terms. The time constant ties them together for a first order sensor such as a thermometer in a well.
In the field you will see these terms as response time on a temperature sensor datasheet and as damping on a smart transmitter. The damping setting of a pressure transmitter adds time constant on purpose to calm a noisy signal.
When a loop looks sluggish, check transmitter damping before you retune the controller. Damping is a time constant you added yourself.
How Do You Calculate a First Order Step Response?
You calculate it with y(t) = y0 + (yf minus y0) × (1 minus 1/e^(t/τ)), where τ is the time constant. After one τ the reading has covered 63.2% of the change.
John Cimbala of Penn State shows in his dynamic system notes that the output reaches about 95% at three time constants and over 99.3% at five. So we treat a sensor as settled after five time constants.
Step from 30 °C to 130 °C, find reading at t = 16 s
t/τ = 16 ÷ 8 = 2, so 1/e² = 0.1353
y = 30 + 100 × (1 minus 0.1353)
Reading = 116.47 °C (86.47% of step)
Dynamic error = 130 minus 116.47 = 13.53 °C
Time to 99% = 4.6 τ = 36.8 s
The curve below plots this example. The last few degrees take as long as the first sixty, which is typical of a first order lag.

If you want a second check on response time, the sensor response time calculator on Zenta Calculator does the same first order maths. For the electrical side of the same exponential curve, see our RC and RL time constant guide.
What Is the Difference Between Static and Dynamic Characteristics?
The main difference is time: static terms are measured after the output settles, while dynamic terms are measured while it is still changing. A good instrument needs both a small static error and a response fast enough for the process.
| Point | Static | Dynamic |
|---|---|---|
| Input type | Constant or very slow | Step, ramp or sine |
| Main terms | Accuracy, precision, linearity, hysteresis | Time constant, lag, fidelity, dynamic error |
| Test method | 5 point calibration up and down | Step test with a timer or recorder |
| Typical unit | % of span or % of reading | Seconds, t0.5, t0.63, t0.9 |
| Fixed by | Zero and span trim, linearisation | Damping, sensor design, thermowell choice |
| Matters most for | Custody transfer, quality, records | Fast loops, trips, alarms |
- Error at each test point
- Hysteresis and linearity
- Zero and span drift
- Settling time after a change
- Lag from thermowell or impulse lines
- Effect of damping on the loop
How to Test Static and Dynamic Characteristics During Calibration
You test static and dynamic characteristics separately: static terms with a five point check rising and falling against a reference, and dynamic terms with a step input and a timer. You can do both on the same bench with a hand pump or a temperature bath.

The reference must be clearly better than the instrument under test, which is the idea behind the test uncertainty ratio of at least 4 to 1. For pressure, a dead weight tester or a good multifunction calibrator serves as the reference.
WIKA explains that IEC 60751 response time tests move the sensor into water flowing at 0.3 m/s or air at 3 m/s, with a temperature step of 10 to 30 K. The results are given as t0.5, t0.63 and t0.9.
For temperature sensors, do the step test with the sensor in the actual thermowell if you can. The air gap between sheath and well bore is often the biggest part of the time constant, as our thermowell guide explains.

Never pass a downscale point and come back up to it. That reversal hides part of the hysteresis loop.
Always write both as found and as left results on the calibration certificate. Labs accredited by NABL under ISO/IEC 17025 also add a measurement uncertainty to every result.
Why Does an Instrument Show Poor Static or Dynamic Performance?
Poor static performance usually comes from drift, wear, wrong ranging or a bad reference, while poor dynamic performance usually comes from added lag. The table lists the symptoms we see most in plants and the first thing to check.
| Symptom | Likely cause | What to check |
|---|---|---|
| Same offset at every point | Zero shift | Zero trim, mounting position |
| Error grows with input | Span error or drift | Span trim, sensor ageing |
| Rising and falling readings differ | Hysteresis or friction | Bourdon tube, linkage, valve packing |
| Output ignores small changes | Dead zone | Gear backlash, positioner dead band |
| Reading trails the process | Large time constant | Thermowell gap, damping value |
If every point is off by the same amount, look at zero and span errors before blaming the sensor. A control loop that hunts around set point can also point to dead band, as covered in control valve hunting.
- Damping set to the value written in the loop design, not left at the factory default
- Sensor spring loaded against the thermowell tip
- Impulse lines free of trapped air or liquid
- Reference standard within its calibration date
Students preparing for GATE can use the video above for the static terms, then try the solved step response example with their own sensor numbers. Our note on instrument accuracy and error has more worked examples.
Static and Dynamic Characteristics FAQ
Static characteristics use a steady input, like 0.5% hysteresis on a 0 to 10 bar transmitter. Dynamic characteristics use a changing input, like an 8 s time constant for an RTD in a thermowell.
You need both static and dynamic characteristics to judge whether an instrument suits a process.
Apply a sudden step input and record the output against time; the time constant is the time to cover 63.2% of the change.
For a step from 30 to 130 °C, note when the reading passes 93.2 °C. If that happens 8 s after the step, τ is 8 s.
After two time constants the reading has covered 86.5% of the step. For a step from 30 to 130 °C with τ of 8 s, the reading at 16 s is 116.47 °C, a dynamic error of 13.53 °C.
That gap keeps shrinking but never quite reaches zero.
Hysteresis is the output difference at one input approached rising and then falling. Dead zone is a band of input change that gives no output change at all.
Both come from friction and backlash, so valve diagnostics often report them as one combined number.
The usual mistake is overshooting a downscale point and coming back up to it. That reversal puts the reading on the rising curve and hides part of the hysteresis, so approach every downscale point from above.
Exercise the instrument over its full range before you start.
For a fast loop such as compressor surge control, dynamic terms matter more because lag delays every correction. Static accuracy still matters, since a fast but drifting transmitter controls tightly to the wrong value.
A small time constant and low damping are the first things to check.
Related Articles
- Instrument Accuracy and Error
- Temperature Sensor Response Time
- Pressure Transmitter Damping and Response Time
- Instrument Calibration Common Terms
- Offset Error, Zero Point Error and Span Error
External References
- Dynamic System Response, J. M. Cimbala, Penn State University (PDF)
- Performance Characteristics of Measuring Instruments, Tutorialspoint
- Time constant, Wikipedia
What We Learn Today
- Static and dynamic characteristics split instrument performance into steady state terms like accuracy and hysteresis and time based terms like lag and time constant.
- A first order sensor covers 63.2% of a step in one time constant, 86.5% in two, 95% in three and over 99.3% in five.
- Static terms are tested with a five point rising and falling calibration, while dynamic terms are tested with a step input and a timer.