ToggleA conveyor belt that wanders off centre can tear its edge on the steelwork. A roller lever switch catches that drift in two steps, first with an alarm and then with a trip, before the damage is done.
A conveyor misalignment switch turns sideways belt drift into an alarm contact and then a trip contact. Here are its angles, PLC wiring, spacing, a drift calculator and a fault finding flowchart.

What is a belt sway switch and how does it work?
Belt sway switch units are roller lever switches fitted in pairs beside a conveyor belt, with the roller just clear of the belt edge. When the belt drifts, its edge pushes the roller and the lever tilts, so a cam opens an alarm contact first (15° on the DUK unit) and a trip contact later (25°), and the PLC stops the drive.
What Is a Belt Sway Switch?
A belt sway switch is a heavy duty roller lever switch mounted beside a conveyor belt that operates when the belt edge drifts sideways and pushes the roller. It gives an early alarm at a small lever angle and stops the conveyor at a larger angle, before the belt rubs the structure and damages its edge.
- Also called a belt misalignment, belt drift or run off switch, and marked BSS on plant drawings.
- Fitted in pairs, one on each side, because the belt can drift either way.
- Two contacts in one housing: first for alarm, second for trip.
- Maximum lever travel is 75° in the Fine Tek SRT and DUK manuals.
You will find these switches on long belt conveyors in cement plants, steel plants, thermal power coal handling plants, ports and mines. They are one part of the protection set in our guide to conveyor safety switches and their types, alongside pull cord, zero speed and chute blockage switches.
Inside the cast housing you get a lever, a roller, a cam and two micro switches, which makes the BSS a rugged cousin of the ordinary limit switch. In the field, most problems come from how the switch is mounted, how its angles are set and how it is wired.
Material spilled from a drifting belt builds up under the return idlers and around the tail pulley, and that build up can push the belt even further off centre.
How Does a Belt Sway Switch Work?
It turns sideways belt movement into lever rotation. The belt edge pushes a free turning roller, the lever tilts about its pivot, and a cam on the shaft operates the alarm contact first and the trip contact later.

The roller turns freely so the moving belt does not grind it, but it still wears, and Fine Tek advises replacing its touch roller after 2 mm of wear. Eaton also offers a maintained action version whose contacts stay operated until someone resets the switch, and an AFAX model for Zone 21 and 22 dust areas.
Belt Misalignment Switch Alarm and Trip Angles
Most belt misalignment switches have two actuation angles, a smaller one for alarm and a larger one for trip. The values differ between makers, so always read them from the manual of the switch you are fitting.
| Switch (source) | First contact | Second contact | Max travel |
|---|---|---|---|
| DUK, Klinkmann manual | 15° | 25° | 75° |
| Fine Tek SRT manual | 20° (reset 18°) | 35° (reset 33°) | 75° |
| Electro Sensors BA100 | 0 to 45° adjustable | 0 to 45° adjustable | 90° each way |
The DUK manual says its leading contact acts at roughly 4 cm of belt displacement and the main contact at roughly 7 cm. You can estimate the same numbers for any switch from its lever length, where R is the pivot to roller contact distance and g is the gap left at installation.
d = g + R × sin θ
Example: g = 25 mm, R = 165 mm
Alarm, 15°: 25 + 165 × 0.259 = 68 mm
Trip, 25°: 25 + 165 × 0.423 = 95 mm
A 165 mm lever fits the DUK figures well, since 165 × sin 15° is about 43 mm and 165 × sin 25° is about 70 mm.

Mark the alarm and trip drift on the stringer with paint during commissioning, so operators can see how close the belt runs to a trip.
How to Wire a Belt Sway Switch to a PLC
Wire each contact to its own PLC digital input through the NC terminals, so the input is ON when the belt is healthy. A drift, a cut cable or a loose terminal then all read as OFF and stop the conveyor.
Each micro switch has common, NO and NC terminals, the same as in pressure switch wiring with NO and NC contacts. On 24 V DC cards, check whether the input is sinking or sourcing before you decide which side of the contact gets the supply.
Fine Tek rates its standard SPDT contact at 15 A for 125 or 250 V AC but only 5 A at 30 V DC. In dusty galleries the cable gland and housing matter as much, and the Fine Tek flameproof model carries an IP67 rating.
- A broken wire trips the belt
- Loose terminal or blown fuse shows at once
- Same fail safe logic as other conveyor trips
- Input turns ON only on drift
- A cut cable stays hidden until a trip fails
- Fit only for a non safety indication
In the PLC, give the alarm channel a message and horn, and give the trip channel an interlock that stops the drive and the feeders upstream. Add a short input filter for contact bounce, as explained in switch debouncing.
Where several switches feed one conveyor, use first out alarm logic so the HMI shows which one tripped first. This ladder logic primer covers the contacts and coils you need.
Many plants also take one trip contact straight into the motor starter circuit, so the belt stops even if the PLC is in program mode. Check your plant philosophy first.
Where to Install Belt Sway Switch Pairs on a Conveyor
Put a pair near the head pulley, near the tail pulley and at each loading point, then add pairs along long runs at the spacing your plant standard sets. Electro Sensors notes that its BA100 pairs usually go near the head end, with the tail and selected points as other options.
No single spacing rule fits every plant. Eaton describes its AFA switches as installed near high risk locations every 300 meters, while a Bulk Online forum user describes a 250 m conveyor with eight switches, four per side.
The DUK manual asks for the middle height of the roller to match the belt edge and for the gap to equal the drift you will accept. Electro Sensors suggests about 1 inch (25 mm) and warns that mounting too close causes false signals.
Coal dust areas need certified housings, so check the hazardous area zone of each gallery and whether the site asks for ATEX or IECEx marking.
Conveyor Switch Count and Drift Calculator
Enter the conveyor length and your pair spacing to get the switch count, and the lever data to get the drift at each contact. The defaults are the numbers from the example above.
Pairs = length ÷ spacing, rounded up, plus one, so both ends are covered. If a pair lands in an awkward spot, shift it to the nearest loading point or curve.
How to Set and Test the Actuation Angle
Set the angle by adjusting the cam on the lever shaft, then tilt the roller by hand and check each contact with a meter and at the PLC. Fine Tek asks for this manual check at regular intervals, not only at commissioning.
It is the same discipline as an instrument loop check, only for a discrete device. Fine Tek warns that loose cover screws let water and dust in, and says not to lubricate the unit.
Why Does a Conveyor Keep Tripping on Belt Sway?
Repeated sway trips usually mean a real tracking problem, such as off centre loading, a misaligned idler or build up on a pulley. The rest come from the switch or its circuit, so work through the flowchart in order.

| Symptom | Likely cause | Field fix |
|---|---|---|
| Trips only when loaded | Off centre chute loading | Align chute and skirts |
| Alarm with belt centred | Gap too small or bent lever | Reset gap, straighten lever |
| No trip on hand test | Cam slipped or contact welded | Reset cam or replace switch |
| Random trips in monsoon | Water in housing or gland | Dry out, change gasket |
After a trip, ask which side tripped and whether the belt was loaded. Those two answers usually point to the chute, the tail pulley or the switch.
For faults inside the panel, follow the PLC troubleshooting steps for the input card. Add the hand test and roller wear check to your preventive maintenance plan.
Belt Sway Switch vs Pull Cord and Zero Speed Switch
A sway switch detects sideways drift, a pull cord switch lets a person stop the belt from the walkway, and a zero speed switch detects slip or a stopped pulley. Each one watches a different fault, so a conveyor needs all three.
| Feature | Sway switch | Pull cord | Zero speed |
|---|---|---|---|
| Detects | Belt drift | Rope pulled | Slow pulley |
| Output | Alarm and trip | Latched trip | Relay or pulses |
| Mounting | Pairs at belt edge | Along walkway | Non drive pulley |
| Reset | Spring or manual | Manual | Automatic |
Read more on the zero speed switch. Pull cord switches belong to the emergency stop function, so they follow the same latching rules as emergency stop push buttons.
- Pairs at head, tail and loading points
- Roller at belt edge height and planned gap
- Angles set and recorded per tag
- NC contacts on separate PLC inputs
- Hand test seen on the drive
Conveyor interlocks come up often in interviews, so try our PLC objective quiz. The Fine Tek manual below lists ratings and maintenance notes.
In this video you can watch a sway switch working on a running conveyor.
Belt Sway Switch FAQ
A sway switch senses belt drift on its own, while a pull cord switch is operated by a person pulling a rope along the walkway.
The sway switch usually resets with a spring, but the pull cord switch latches and needs a manual reset at the switch.
Use d = g + R × sin θ, where g is the roller gap, R the lever length and θ the contact angle.
With a 25 mm gap and 165 mm lever, the alarm at 15° acts at 68 mm drift and the trip at 25° acts at 95 mm drift.
Wire them NC so the input is ON when the belt is healthy. A drift, a cut cable or a lost supply then all turn the input OFF and stop the conveyor.
An NO circuit hides a broken wire until a real drift fails to trip.
Check the roller gap first, because a gap set too small lets normal belt wander reach the alarm angle. Then look for a bent lever, a slipped cam or water in the housing.
If the contact tests closed, check the cable cores and the input fuse.
Choose a dust ignition proof model certified for the gallery zone, with IP67 sealing and at least two contacts.
A maintained version that needs a local reset helps when the plant wants a site check of the belt after every trip.
Related Articles
- Conveyor Safety Switches and Their Types
- Zero Speed Switch Working Principle
- What Is a Limit Switch
- Sinking and Sourcing in PLC
- Emergency Stop Push Buttons
External References
- Fine Tek SRT Conveyor Belt Misalignment Switch Manual (PDF)
- Eaton AFA Conveyor Belt Alignment Switches
- Conveyor belt, Wikipedia
What We Learn Today
- A belt sway switch turns sideways belt drift into lever rotation, opening an alarm contact first and a trip contact at the larger angle.
- Belt drift at each contact follows d = g + R × sin θ, so the roller gap and lever length decide how early the switch acts.
- Fit switches in pairs at head, tail and loading points, wire NC contacts to separate PLC inputs and test them by hand regularly.