Communication
Modbus Register Map: 0x, 1x, 3x and 4x Tables, 40001 vs Offset 0, Float Word Order, Scaling and an Address Calculator

A device can talk perfectly on the bus and still show garbage on the SCADA screen because one line of its register table was read the wrong way. This article shows how to read any vendor table, convert 40001 style numbers to offsets and decode floats correctly.

0x 1x 3x 4x Tables 40001 vs Offset 0 Float Word Swap Scaling Address Calculator

Every Modbus slave publishes a table that tells the master where each value lives and how to decode it. Learn the four tables, the off by one trap, 32 bit floats and integer scaling with solved examples and a calculator.

Hello everyone, today we are going to learn how to read a modbus register map, convert 40001 style addresses to protocol offsets and decode floats without guesswork.
modbus register map

What Is a Modbus Register Map?

A modbus register map is the table in a device manual that lists every value the device shares, with its address, data type, scaling, units and read or write access. The master uses this table to build each request, so a wrong address, data type or word order gives wrong readings even when communication is healthy.

Quick Answer
  • Four tables: coils (0x), discrete inputs (1x), input registers (3x) and holding registers (4x)
  • 40001 is a documentation number; the request carries offset 0 with function code 03
  • Each register is 16 bits, so a 32 bit float or long integer uses two registers
  • Word order (ABCD, CDAB, BADC, DCBA) must match the device
  • Integer values often need a scale factor such as divide by 10 or 100

The protocol itself only moves bits and 16 bit words, as covered in our page on how the Modbus protocol works. The meaning of each word comes from the vendor table, and the master chooses which table to read through the Modbus function codes it sends.

Moxa MGate MB3180 Modbus gateway that maps Modbus TCP requests to serial register addresses
Image credit: Moxa. Product photo courtesy of Moxa, shown here for educational reference.

A gateway like the one above passes requests between Modbus TCP and RTU, but it never fixes a wrong address in the master. The same modbus register map rules apply whether the slave sits on Ethernet or on a serial line, which we compare in Modbus RTU vs Modbus TCP.

Advertisement

The Four Tables: 0x, 1x, 3x and 4x

The SEL white paper on register addressing traces the numbering back to Modicon PLCs, which grouped data into four ranges and used the leading digit as a type marker. NI adds that Modbus natively supports only two data types, a Boolean bit and an unsigned 16 bit word, and that each table can hold up to 65,536 elements.

TableClassic RangeSizeAccessRead FCWrite FC
Coils (0x)00001 to 099991 bitRead and write0105, 15
Discrete inputs (1x)10001 to 199991 bitRead only02None
Input registers (3x)30001 to 3999916 bitsRead only04None
Holding registers (4x)40001 to 4999916 bitsRead and write0306, 16

Most instruments put measured values in input registers and setpoints in holding registers. Many modern devices, however, publish everything as holding registers, so always follow the actual modbus register map rather than the habit of the last device you used.

Do You Know?

NI notes that the four tables are only a conceptual model. A slave is allowed to share the same memory between holding and input registers, so reading offset 10 with function code 03 or 04 may return the same value on some devices.

Modbus 40001 vs Offset 0: Why Addresses Look Off by One

The number 40001 never travels on the wire. The SEL paper explains that each table is indexed from raw address 0, the function code selects the table, and the Modicon number is only a documentation convention.

So holding register 40001 is sent as function code 03 with starting address 0, and 40108 is sent as address 107. Six digit numbering such as 400001 to 465536 was added later so that documents could reach the full 16 bit address space.

Solved example: float at 40108 and 40109
Offset = 40108 minus 40001
Offset = 107 = 0x006B
Request: FC 03, start 107, quantity 2
Last register read = offset 108
Quick Tip

Before you configure 50 tags, read one known value such as the device serial number or a fixed firmware version. If it only appears when you add or remove 1 from the address, you have found the convention of that vendor in two minutes.

Modbus Address to Offset Calculator
Table, function code and protocol offset
Holding register, FC 03, offset 107 (0x006B) to 108

The calculator handles both 5 and 6 digit styles and limits the quantity to 125, which is the largest number of registers that function code 03 or 04 can return in one request. If your manual already lists raw offsets starting at 0, simply skip the subtraction.

Modbus Register Map Data Types

A 16 bit word on its own carries no meaning, and the SEL paper calls each vendor interpretation a variation. The data type column of the table tells you how to turn one or more words into an engineering value, and our article on PLC data types covers the same types from the PLC side.

UINT16 and INT16

One register holding 0 to 65535 unsigned, or minus 32768 to 32767 signed.

Best for: Status words, counts, scaled values
1 register
UINT32 and INT32

Two registers joined into one 32 bit integer, high word first on most devices.

Best for: Totalisers, energy counters, hours
2 registers
FLOAT32

IEEE 754 single precision with 1 sign bit, 8 exponent bits and 23 mantissa bits.

Best for: Flow, pressure, temperature values
2 registers
Bit Field

Each bit of one register is a separate flag, such as alarm or fault.

Best for: Diagnostics and alarm words
1 register
ASCII String

Two characters per register, used for tags and model names.

Best for: Device tag, serial number
N registers

Older energy meters sometimes still use binary coded decimal, which looks like a normal integer until the value passes 9. When the data type column is blank, ask the vendor before you guess, because a wrong guess can still give believable numbers.

How to Read Float Values From Two Modbus Registers

A 32 bit float needs two consecutive 16 bit registers, and the device decides which register holds the high word. The SEL paper shows that the same pair 0x1234ABCD decodes to a tiny number, 5.7 divided by 10²⁸, in one order and to a completely different value in the other.

Order NameRegisters as SentValue DecodedTypical Use
ABCD (big endian)42F6, E666123.45Modbus default, most meters
CDAB (word swap)E666, 42F6about minus 2.7 × 10²³Many PLCs and drives
BADC (byte swap)F642, 66E6about minus 9.9 × 10³²Some gateways
DCBA (little endian)66E6, F642about 5.5 × 10²³PC based software

The values above all come from the same float 123.45, which is 0x42F6E666 in IEEE 754 form. Chipkin lists these four orders by name, and a wild exponent almost always means the order setting in the master is wrong, not the device.

Advertisement

How to Read a Vendor Modbus Register Map

1
Find the Base
Check if the table lists 40001 style numbers, 1 based registers or raw offsets from 0.
2
Check the Table
Note whether each value is an input register or a holding register.
3
Read the Data Type
Mark INT16, UINT32, FLOAT32 or string, and how many registers each uses.
4
Note Word Order
Look for a float or long word order setting in the device menu.
5
Find Scale and Units
Record any multiplier, divisor or decimal point register.
6
Test One Point
Read a known value first, then build the rest of the tag list.

Write the result into an instrument IO list with columns for offset, function code, data type, order and scale. That single sheet becomes the modbus register map for your own system and saves hours during commissioning.

Scaling Integer Registers to Engineering Units

Many field devices send integers because they are simple and compact, so a pressure of 12.34 bar might arrive as 1234. The register table then states a scale factor, or the device publishes a separate register that sets the decimal point.

Solved example: span scaling
Raw range 0 to 10000 = 0 to 16 bar
Raw value read = 6250
Value = 6250 × 16 ÷ 10000
Value = 10.0 bar

This is the same linear math used in PLC analog scaling, and you can check it quickly with our PLC raw count calculator. Keep the scale factor of every modbus register map entry in the tag database, not hidden inside HMI scripts.

Myth: If the slave answers without an exception code, the address must be right.
Fact: A wrong offset often points to a valid neighbouring register, so the slave answers happily with the wrong value.
Myth: A float can be read from any single register.
Fact: A float always needs two consecutive registers read together in one request, or the two halves may come from different moments.
Myth: Word order is part of the Modbus standard.
Fact: The standard defines only 16 bit registers, so word order for 32 bit values is chosen by each vendor.
Float32 Registers: Advantages
  • Value arrives in real engineering units
  • No scale factor to look up
  • Wide range from tiny to very large values
  • Easy to read on any modern SCADA
Float32 Registers: Drawbacks
  • Uses two registers for every value
  • Word order mismatch gives wild numbers
  • Older masters may not support floats
  • Precision drops for very large totals

A free SCADA package and a USB to RS485 adapter are enough to test any modbus register map at your desk before site work. Our industrial protocol gateway guide also explains how gateways remap addresses between networks.

Modbus Register Map Troubleshooting Table

SymptomLikely CauseFix
Value belongs to the next tagOff by one between 40001 and offset 0Add or subtract 1 from the start address
Huge or tiny float like 1E+38Word or byte order mismatchTry CDAB, then BADC, then DCBA
Value 10 or 100 times too bigScale factor missingApply the divisor from the table
Negative value shows 65000 or moreSigned INT16 read as unsignedChange data type to INT16
Exception code 02Address outside the table rangeCheck offset and quantity limits

If nothing answers at all, the problem is wiring, baud rate or slave ID, not the modbus register map. Work through our Modbus RTU troubleshooting steps and check the RS485 termination and biasing first.

Quick Tip

Write values to holding registers only after you have read them correctly. A wrong offset on a write can change a range or a unit setting instead of a setpoint, so test writes with the process in a safe state.

Do You Know?

Chipkin calls off by one addressing the number one integration issue in Modbus work. That is why many master drivers offer a simple checkbox for zero based or one based addressing.

Advertisement

Field Checklist Before You Commission

  • Base convention of the modbus register map confirmed with one known value
  • Correct function code for each table
  • Data type and register count noted for every tag
  • Float and long word order set in the master
  • Scale factors and units recorded in the tag list
  • Block reads kept within 125 registers
  • Write access limited to the registers you really need
PDF
SEL White Paper: Modbus Register Addressing and Data Type Variations
Schweitzer Engineering Laboratories, LWP0020, free PDF

If you prefer to watch before you read a modbus register map on site, the short video below walks through the Modbus data model and registers in plain language.

Modbus Register Map FAQ

What is the difference between 40001 and 400001 in Modbus?

Both numbers point to the first holding register, which is sent as offset 0 with function code 03. The 5 digit style reaches register 49999 while the 6 digit style reaches 465536.

The 6 digit form was added so documents could use the full 16 bit address space. Your master only needs the offset, so the style of the manual does not change the request.

What is a holding register in Modbus?

A holding register is a 16 bit word that the master can read with function code 03 and write with codes 06 or 16. It usually stores setpoints, configuration values and often process values too.

In the classic numbering, holding registers appear as 40001 to 49999. Always check the modbus register map of your device, because many meters publish measured values here as well.

What is the difference between input register and holding register?

An input register is read only and is read with function code 04, while a holding register can be read and written. Input registers suit live measurements that the master should never change.

Holding registers carry setpoints and settings that the master may adjust. Some devices share memory between the two tables, so the same value may appear in both.

How many registers does a float use in Modbus?

A 32 bit IEEE 754 float uses two consecutive 16 bit registers. Both registers should be read in a single request so the two halves belong to the same sample.

A 64 bit double precision value uses four registers. The device manual or its word order setting tells you which register holds the high part of the number.

Why is my Modbus value off by one register?

The manual probably uses 1 based numbering such as 40001, while your master expects the raw offset that starts from 0. The slave then returns the neighbouring register without any error.

Read one known value and shift the address by 1 until it appears. Many drivers have a zero based or one based option that fixes every tag at once.

What is word swap in Modbus?

Word swap means the two 16 bit registers of a 32 bit value arrive with the low word first, often called CDAB order. Reading them in the default order gives a wild number with a huge exponent.

The fix is to change the word order setting in the master or in the device. Test with a known value such as a fixed setpoint before trusting the live readings.

Advertisement

Related Articles

External References

What We Learn Today

  • A modbus register map lists address, table, data type, scale and access for every value, and the master needs all five to read correctly.
  • Documented numbers such as 40001 are sent as offset 0, so subtract the table base and pick function code 03 or 04 to match.
  • Floats use two registers in a vendor chosen word order, and scaled integers need the divisor from the table before display on SCADA.
I hope you like above blog. There is no cost associated in sharing the article in your social media. Thanks for reading!! Happy Learning!!
Sunayana Gadepatil, author at Instrumentation Blog
Author · instrumentationblog.in
Ms. Sunayana Gadepatil is an instrumentation professional, technical writer, and the author behind Instrumentation Blog. With a strong interest in industrial instrumentation, process measurement, and automation, she specializes in simplifying complex technical concepts into clear, practical, and easy to understand insights. Through her articles, Ms. Sunayana shares valuable knowledge on flow, pressure, level, temperature, control systems, and industrial automation for engineers, students, technicians, and industry professionals.