OC and SC Test of Transformer: Diagram, Formula & Calculator

Share:
Electrical Machines
OC and SC Test of Transformer: Open Circuit and Short Circuit Test Connections, Core Loss, Copper Loss, Equivalent Circuit, Efficiency, Regulation and Calculator

Two simple tests with a wattmeter, ammeter and voltmeter reveal almost everything about a transformer. Here you will see how each test is connected, what every reading means and how to turn the numbers into efficiency and regulation.

Open Circuit Test Short Circuit Test Connection Table Efficiency and Regulation Calculator

The open circuit and short circuit tests let you find losses and the equivalent circuit without loading a transformer. Learn the connections, formulas, a fully solved example and the field mistakes that spoil results.

Hello everyone, today we are going to learn the OC and SC test of transformer, with connection diagrams, formulas, a solved example and a calculator.
oc and sc test of transformer
        title=

What Is the OC and SC Test of Transformer?

The OC and SC test of transformer is a pair of no load and short circuit measurements that find core loss, copper loss and the equivalent circuit parameters without loading the transformer fully. The open circuit test is done on the LV side at rated voltage, and the short circuit test is done on the HV side at rated current with the LV winding shorted.

Quick Answer
  • OC test: LV side energised at rated voltage, HV open
  • OC test gives core loss and magnetising branch Rc and Xm
  • SC test: HV side at rated current, LV shorted
  • SC test gives full load copper loss, Req, Xeq and % impedance
  • Together they give efficiency and voltage regulation at any load

Because each test supplies only the losses, the power drawn from the lab supply is tiny compared with the rating. That is the main reason these indirect tests are used for large units, where a real full load test would waste a lot of energy.

Advertisement

Open Circuit Test of Transformer

In the open circuit test, also called the no load test, a voltmeter, ammeter and wattmeter are connected on the LV winding and the HV winding is left open. Rated voltage at rated frequency is applied through a variac, and the three readings are noted.

Open circuit or no load test connection diagram of a transformer with wattmeter, ammeter and voltmeter on the LV side
Image credit: Electrical Easy. Diagram courtesy of Electrical Easy, shown here for educational reference.

Since the no load current is only a few percent of rated current, copper loss in the winding is negligible. Electrical Easy and Electrical4U both note that the wattmeter reading is therefore taken as the core loss, made of hysteresis and eddy current loss.

OC test readings: V0, I0, W0
cos φ0 = W0 ÷ (V0 × I0)
Iw = I0 cos φ0, Iμ = I0 sin φ0
Rc = V0 ÷ Iw
Xm = V0 ÷ Iμ

The two currents represent the core loss component and the magnetising component of the no load current. The values of Rc and Xm found this way are referred to the LV side, because that is where the meters were connected.

Do You Know?

The OC test is done on the LV side simply for safety and convenience. Rated LV voltage, such as 250 V, is easy to apply in a lab, while rated HV voltage would need a high voltage source and meters.

Short Circuit Test of Transformer

In the short circuit test, also called the impedance test, the LV winding is shorted with a thick link and the meters are placed on the HV side. The voltage is raised slowly from zero until the ammeter reads rated HV current.

Electrical4U notes that only about 5 to 10 % of rated voltage is needed to drive rated current. At this low voltage the core flux is very small, so core loss is neglected and the wattmeter reads full load copper loss.

SC test readings: Vsc, Isc, Wsc
Zeq = Vsc ÷ Isc
Req = Wsc ÷ Isc²
Xeq = √(Zeq² minus Req²)
% Z = Vsc ÷ Vrated × 100

These series values are referred to the HV side and form the approximate equivalent circuit. The percentage impedance from this test is the same figure used later when you calculate short circuit fault current on the LV bus.

Quick Tip

Never apply full voltage with the LV side shorted. Always start the variac at zero and raise it slowly while watching the ammeter, stopping exactly at rated current.

OC and SC Test Connection Table

The table compares both tests side by side, which is the quickest way to remember the OC and SC test of transformer for exams and for site work.

PointOpen Circuit TestShort Circuit Test
Meters onLV sideHV side
Other windingOpenShorted
AppliedRated voltage5 to 10 % voltage, rated current
Current2 to 5 % of rated (no load)Rated current
Wattmeter readsCore (iron) lossFull load copper loss
GivesRc, Xm, no load PFReq, Xeq, Zeq, % impedance
Loss neglectedCopper lossCore loss
Wattmeter typeLow power factor wattmeterNormal wattmeter

A low power factor wattmeter is used in the OC test because the no load power factor is often only 0.1 to 0.3. A normal wattmeter would read near the bottom of its scale and give poor accuracy.

Advertisement

Solved Example of OC and SC Test

Take a 25 kVA, 2500 V / 250 V single phase transformer, the same values used as defaults in the calculator below. Rated HV current is 25000 ÷ 2500 = 10 A.

OC test on LV: 250 V, 1.4 A, 105 W
cos φ0 = 105 ÷ (250 × 1.4) = 0.3
Iw = 0.42 A, Iμ = 1.336 A
Rc = 250 ÷ 0.42 = 595.2 Ω
Xm = 250 ÷ 1.336 = 187.2 Ω
SC test on HV: 125 V, 10 A, 320 W
Zeq = 125 ÷ 10 = 12.5 Ω
Req = 320 ÷ 100 = 3.20 Ω
Xeq = √(156.25 minus 10.24) = 12.08 Ω
% Z = 125 ÷ 2500 × 100 = 5 %

To refer Rc and Xm to the HV side, multiply them by the square of the turns ratio, here 10² = 100. Our page on transformer turns ratio explains why impedances scale with the square of that ratio.

Efficiency and Regulation From OC and SC Test

Once core loss and full load copper loss are known, efficiency at any load and power factor follows directly. Copper loss changes with the square of the load fraction, while core loss stays constant.

Efficiency at full load, PF 0.8
Output = 25 × 0.8 = 20 kW
Losses = 105 + 320 = 425 W
η = 20000 ÷ 20425 = 97.92 %
Regulation at full load, PF 0.8 lag
% R = I (Req cos φ + Xeq sin φ) ÷ V × 100
= 10 (3.2 × 0.8 + 12.08 × 0.6) ÷ 2500 × 100
= 3.92 %

Maximum efficiency occurs when copper loss equals core loss, at a load fraction of √(105 ÷ 320), or about 57 % of rating. Our article on transformer efficiency calculation shows how to plot the full efficiency curve from these two numbers.

5 to 10 %Voltage needed in SC test
2 to 5 %Typical no load current
57 %Load for maximum efficiency in example
3.92 %Regulation at full load, 0.8 PF

OC and SC Test Calculator

Enter the rating, the three OC readings, the three SC readings and the load power factor. The SC readings must be taken at rated HV current for the efficiency and regulation to be correct.

OC and SC Test Calculator
Equivalent circuit and performance
Rc 595.2 Ω, Xm 187.2 Ω (LV side); Req 3.20 Ω, Xeq 12.08 Ω (HV side); regulation 3.92 %, efficiency 97.92 %

The defaults reproduce the solved example above exactly. Change the PF to 1 to see regulation drop and efficiency rise, which is typical for resistive loads.

Step by Step Procedure for Both Tests

1
Check Nameplate
Note kVA, HV and LV voltages and rated currents of each winding.
2
Wire OC Test
Meters and variac on LV, HV terminals open and insulated.
3
Read OC Values
Raise to rated LV voltage, note V0, I0 and W0.
4
Wire SC Test
Short LV with a heavy link, meters and variac on HV.
5
Read SC Values
Raise slowly to rated HV current, note Vsc, Isc and Wsc.
6
Calculate
Find Rc, Xm, Req, Xeq, then efficiency and regulation.

The VSSUT Electrical Machine Lab I manual follows exactly this order on a 3 kVA, 230/230 V single phase transformer, using an autotransformer to set voltage and current. Many Indian university labs use a similar setup for the OC and SC test of transformer in the third year.

Before any test, it is good practice to do an insulation resistance test on each winding. A weak winding can fail when energised, which damages instruments and the variac.

PDF
VSSUT Burla: Electrical Machine Lab I Manual
University lab manual with the OC and SC experiment on a single phase transformer

OC and SC Test in Factory and Field Practice

In factories the same measurements appear as routine tests, called no load loss and current measurement and load loss and short circuit impedance measurement in IEC 60076 1. Our guide on transformer routine and type tests lists where they sit among the other tests.

For 3 phase units, a 3 phase supply and three wattmeters or a power analyser are used, and load loss is corrected to a reference temperature. The vector group does not change the method, but you should confirm it first using transformer vector group markings.

Design Verification
Confirms losses guaranteed in the purchase order before dispatch.
Efficiency Class Check
Measured losses decide the energy efficiency level of a distribution transformer.
Fault Level Studies
The % impedance from the SC test feeds protection and fault calculations.
Condition Monitoring
A rise in no load current over the years can point to core problems.
Parallel Operation
Units with matching % impedance share load fairly when paralleled.

Units that will run in parallel must have close % impedance values, which our article on the per unit system helps you compare on a common base. Tap position matters too, so note it if the unit has an on load tap changer.

Advantages of OC and SC Test
  • Needs only a small fraction of rated power
  • Separates core loss and copper loss clearly
  • Gives the full equivalent circuit
  • Predicts efficiency and regulation at any load
Limitations
  • Does not show temperature rise under real load
  • Ignores stray load loss variation with real load
  • Core loss in SC test and copper loss in OC test are assumed zero
  • Needs accurate low power factor wattmeters
Myth: The SC test is done at rated voltage with the LV shorted.
Fact: Rated voltage on a shorted winding would cause a fault. Only 5 to 10 % voltage is needed for rated current.
Myth: The OC test must be done on the HV side.
Fact: Either side works in theory, but the LV side is used because its rated voltage is safer and easier to supply.
Myth: OC test current is close to rated current.
Fact: No load current is only a small percentage of rated current, which is why copper loss is ignored.

Common Errors and Field Tips

  • Use a low power factor wattmeter for the OC test
  • Make the LV short with a link rated for full LV current
  • Raise SC voltage slowly from zero, never switch on at full
  • Record winding temperature with the SC readings
  • Check the variac rating against rated HV current
  • Keep HV terminals guarded during the OC test, since they rise to rated HV voltage
Do You Know?

During the OC test the open HV terminals sit at full rated HV voltage, even though nothing is connected to them. Students often forget this, so the HV side must always be guarded.

Inrush current can also trip the supply when the OC test is switched on directly at rated voltage, a topic covered in transformer inrush current. Starting the variac from zero avoids this problem completely.

Advertisement
Quick Tip

If OC power factor comes out above 0.5, recheck the wattmeter connections and scale. A healthy transformer core normally gives a low no load power factor.

Before starting any lab or site test, go through the electrical safety audit checklist for the test area. For regular upkeep after testing, our transformer maintenance checklist is a useful next step.

OC and SC Test of Transformer FAQ

Why is the OC test done on the LV side?

The open circuit test is done on the low voltage side because its rated voltage is easier and safer to apply. Meters of normal range can then be used for the voltage and current readings.

The high voltage winding stays open, so no load current flows in it. The core flux is the same from either side, so core loss does not change.

Why is the SC test done on the HV side?

Rated current on the high voltage side is much smaller than on the low voltage side. This lets the lab use a normal ammeter and a smaller variac for the test.

Only a few percent of rated voltage is needed, which is easy to supply on that side. The low voltage winding is shorted with a heavy copper link.

What does the OC test of a transformer measure?

The open circuit test measures the core loss, made of hysteresis and eddy current loss in the steel. It also measures the no load current and the no load power factor of the transformer.

From these readings you can find the core loss resistance and the magnetising reactance. Together they form the shunt branch of the approximate equivalent circuit used in calculations.

What does the SC test of a transformer measure?

The short circuit test measures the full load copper loss in both windings together. It also gives the equivalent resistance, reactance and percentage impedance.

These are series values referred to the side where the meters are connected during the test. Engineers use them to calculate voltage regulation, fault level and load sharing between transformers in parallel.

Why is core loss neglected in the SC test?

The applied voltage is only about 5 to 10 % of rated, so the core flux is very low. Core loss varies roughly with the square of flux, so it becomes negligible.

The wattmeter reading is therefore taken as copper loss alone in the windings. This assumption makes the OC and SC test of transformer simple and accurate enough.

How is efficiency found from OC and SC test results?

Add the core loss from the open circuit test to the copper loss at the chosen load. Copper loss at any load equals full load copper loss times the square of load fraction.

Efficiency is output divided by output plus these total losses, expressed in percent. Maximum efficiency occurs when copper loss equals the constant core loss value.

Advertisement

Related Articles

External References

What We Learn Today

  • The OC and SC test of transformer finds core loss on the LV side at rated voltage and copper loss on the HV side at rated current.
  • Open circuit readings give the magnetising branch Rc and Xm, while short circuit readings give Req, Xeq and the percentage impedance.
  • Using both losses together, you can calculate efficiency and voltage regulation at any load and power factor without a real full load test.
I hope you like above blog. There is no cost associated in sharing the article in your social media. Thanks for reading!! Happy Learning!!
Author · instrumentationblog.in
Editorial Staff
Instrumentation Blog’s Editorial Staff are industry professionals and technical writers with a strong interest in industrial electrical systems. They specialize in simplifying complex technical concepts into clear, practical, and easy to understand insights. All articles written by the Editorial Staff are technically reviewed before publication.