VFD Sizing: 7 Proven Steps to Pick the Right Drive Safely

Share:
Motors & Drives
VFD Sizing: 7 Proven Steps to Pick the Right Drive Safely

A drive chosen only by the kW printed on the motor often trips, overheats or fails early in a hot Indian plant room. Sizing it by current, duty and site conditions gives a drive that starts the load every time and lasts for years.

Motor Current Normal vs Heavy Duty Derating Cable Length

VFD sizing means choosing a drive whose continuous current and overload capacity match the motor and load under real site conditions. This guide explains current based selection, duty ratings, derating and a worked calculator.

Hello everyone, today we are going to learn how VFD sizing works, why current matters more than kW, how duty ratings and derating change the choice and how to calculate the drive rating.
VFD sizing

What Is VFD Sizing?

VFD sizing is the process of selecting a variable frequency drive whose continuous output current, overload capacity and environmental rating suit the motor and the driven load at the actual site. A variable frequency drive converts fixed mains supply into variable voltage and frequency, and its power devices have strict current and temperature limits.

The kW value in a drive catalogue is only a guide for a typical 4 pole motor at nominal voltage. Real motors differ in efficiency, poles and power factor, so their current can be higher than the catalogue assumes.

Illustration of VFD derating for installation altitude from VFDs.com
Image credit: VFDs.com. Illustration courtesy of VFDs.com, shown here for educational reference.

Good VFD sizing therefore starts from the motor nameplate current, not the kW, and then adds the load duty and site conditions. Read the nameplate carefully, as explained in motor full load current.

Advertisement

Why Current Matters More Than kW in VFD Sizing

ABB Technical Guide No 7, Dimensioning of a drive system, tells engineers to choose the drive according to the dimensioning current, calculated from the load torque profile. The drive must supply that current continuously and also cover short overloads.

A 6 pole or 8 pole motor of the same kW draws more current than a 4 pole motor, because its power factor is lower. Older or rewound motors and low efficiency designs, compared in IEC 60034 efficiency classes, can also draw more current than the catalogue figure.

Do You Know?

In ABB guide examples, a 6 pole 55 kW motor needed 19 A less current than a 4 pole 75 kW motor for the same extruder duty. A sensible motor choice can shrink the drive as well.

Normal Duty vs Heavy Duty in VFD Sizing

Most drive makers publish two current ratings for each frame. ABB defines light duty current for the ACS580 as allowing 110 percent overload for 1 minute every 5 minutes, and heavy duty current as allowing 150 percent overload for 1 minute every 5 minutes.

Duty ClassOverload ExampleTypical LoadsEffect on VFD Sizing
Normal or light duty110 percent for 1 minuteCentrifugal pumps, fans, blowersUse the higher continuous current rating
Heavy duty150 percent for 1 minuteConveyors, crushers, mixers, hoists, extrudersUse the lower heavy duty rating, often one frame larger
High starting torqueAbove 150 percent brieflyLoaded conveyors, positive displacement pumpsCheck peak current and starting time with the maker

Variable torque loads such as fans need little torque at low speed, so normal duty is usually enough. Constant torque loads need full torque from standstill, so their VFD sizing must use the heavy duty current, which is why such drives often trip as described in VFD overload trip causes.

Quick Tip

When in doubt about the load type, ask the mechanical team for the starting torque and acceleration time. A crusher restarting full of material needs far more current than a free running pump.

7 Proven Steps for Correct VFD Sizing

1
Collect Motor Data
Note nameplate current, voltage, kW, poles and service factor.
2
Define the Load
Classify as variable or constant torque and note starting torque.
3
Choose Duty Rating
Pick normal duty or heavy duty from the overload need.
4
Apply Derating
Correct for ambient temperature, altitude and switching frequency.
5
Check Supply
Confirm voltage, phases and supply capacity for the drive.
6
Review Cable and Filters
Check motor cable length, reactors and dV/dt filters.
7
Select Accessories
Add braking resistor, input reactor and enclosure as needed.

Step one should use the motor current at the actual supply voltage. In India, motors are often rated at 415 V, so check the nameplate column for that voltage, and follow the drive setup advice in VFD parameter configuration.

Steps four to six are where most VFD sizing mistakes happen in the field. A drive that is correctly sized on paper can still overheat in a hot rooftop panel or trip on a long cable run.

VFD Sizing Derating for Heat and Altitude

Drive ratings are normally given at 40 °C ambient and up to 1000 m altitude. ABB specifies a 1 percent derate per 100 m above 1000 m for the ACS580, up to 4000 m.

40 °CUsual rated ambient
1000 mAltitude before derating
1 percentDerate per 100 m above 1000 m
1 percentDerate per °C above 40 °C, Galt G500 example

VFDs.com cites the Galt G500 manual, which asks for a 1 percent derate for every degree above 40 °C and does not allow operation above 50 °C. Air at high altitude is thinner and cools less, an effect also seen in altitude effects on instrumentation.

Do You Know?

VFDs.com calculates that a drive at 2500 m needs a 15 percent derate, so a 180 A unit can deliver only 153 A. A mine site near 4000 m would face about 30 percent.

VFD Sizing Formula

Temperature factor kT = 1 minus 0.01 × (T minus 40), when T is above 40 °C
Altitude factor kA = 1 minus 0.01 × (H minus 1000) ÷ 100, when H is above 1000 m
Required drive current = motor FLC ÷ (kT × kA)

Example: FLC = 28 A, T = 45 °C, H = 1500 m
kT = 1 minus 0.05 = 0.95
kA = 1 minus 0.05 = 0.95
kT × kA = 0.9025
Required drive current = 28 ÷ 0.9025 = 31.0 A

In this VFD sizing example, choose a drive whose rated current at the chosen duty is at least 31.0 A in this example. Always confirm the actual derating curves in the manual of the drive you buy, because each maker publishes its own.

VFD Sizing Calculator

Required Drive Current After Derating
Result
Derate factor 0.90, required drive current 31.0 A at the chosen duty
Advertisement

Second Worked Example: Single Phase Supply

A farm workshop has only single phase supply and wants to run a 3 phase motor with a nameplate current of 9 A. VFDs.com gives the safe rule of doubling the motor current when a 3 phase drive is fed from single phase, so the drive needs an 18 A three phase rating.

The input rectifier and DC bus capacitors carry much higher ripple on single phase, which is why the derate is so large. The difference in supply types is covered in single phase vs three phase power.

Switching Frequency and Motor Cable Length

A higher switching frequency makes the motor quieter but raises switching losses in the IGBTs, so most makers derate output current at higher carrier settings. ABB lists 1, 4, 8 and 12 kHz options for smaller ACS580 frames, so check the manual for the current allowed at each setting.

Long motor cables add capacitance, so the drive supplies extra charging current and the motor sees voltage spikes from reflected waves. Check the maximum cable length in the manual and add an output reactor or a dV/dt filter when the run is long.

Cable size also matters for voltage drop and heating, using the same method as in cable sizing for motor feeders. Use symmetrical shielded cable for good EMC behaviour.

Quick Tip

If a drive must sit far from the motor, place it so the motor cable stays within the limit and run the longer section on the supply side. Supply cables carry no high frequency switching edges.

Load Types and Their VFD Sizing Approach

Centrifugal Pumps and Fans

Torque rises with speed squared, little starting torque.

Best for: normal duty rating
Variable Torque
Conveyors and Mixers

Full torque at all speeds, high breakaway.

Best for: heavy duty rating
Constant Torque
Hoists and Cranes

Overhauling loads that regenerate energy.

Best for: heavy duty with braking resistor
Regenerative
Multi Motor Drives

One drive feeding several motors in parallel.

Best for: sum of currents plus margin
Group Drive

For hoists and quick stopping machines, regenerated energy must go somewhere, so VFD sizing must include the braking chopper and resistor, described in VFD braking resistor sizing. Group drives need individual motor overload protection because the drive cannot protect each motor separately.

Myth: Match the drive kW to the motor kW and you are done.
Fact: Size by current, duty, derating and cable length, not only by kW.
Myth: A bigger drive is always safer.
Fact: A greatly oversized drive costs more and may protect the motor poorly.
Myth: Derating applies only above 50 °C.
Fact: Most drives derate above 40 °C ambient and 1000 m altitude.
Myth: Fans and conveyors need the same rating.
Fact: Conveyors need heavy duty overload capacity, while fans usually need normal duty.
Benefits of Correct VFD Sizing
  • Reliable starting under full load.
  • Fewer overload and overtemperature trips.
  • Longer IGBT and capacitor life.
  • Lower capital cost than heavy oversizing.
  • Correct motor protection settings.
Risks of Poor Sizing
  • Undersized drives trip during acceleration.
  • Hot panels shorten drive life.
  • Oversized drives waste money and panel space.
  • Long cables damage motor insulation.
  • Harmonics overload the supply transformer.
Advertisement

Supply Side Checks for VFD Sizing

A 6 pulse drive draws non sinusoidal current, so many drives on one transformer raise harmonic distortion. Use input reactors or DC chokes and consider an active harmonic filter when the drive load is a large share of the transformer rating.

The upstream breaker or fuse must suit the drive input current and the maker recommendation, as shown in fuse selection guide. Harmonic effects on other plant equipment are explained in power quality issues with VFDs and PLCs.

VFD Sizing Checklist Before Ordering

  • Motor nameplate current at site voltage recorded.
  • Load type and starting torque confirmed.
  • Normal or heavy duty rating selected.
  • Ambient temperature and altitude derating applied.
  • Switching frequency and its derating checked.
  • Motor cable length within limit or filter added.
  • Braking need reviewed for stopping and lowering loads.
  • Enclosure IP rating and panel ventilation planned.

Motor insulation should suit inverter duty, especially on older motors, as discussed in motor insulation classes. A careful VFD sizing review at this stage avoids costly replacements after commissioning.

ABB Technical Guide on Drive Dimensioning

PDF
ABB Technical Guide No 7, Dimensioning of a Drive System
ABB Drives guide with worked dimensioning examples

How to Size and Select a Drive, Video Guide

VFD Sizing FAQ

What is VFD sizing?

It is the selection of a drive whose current, overload capacity and environmental rating suit the motor and the load. It always starts from the motor nameplate current and the type of load.

Site conditions such as heat, altitude and cable length then adjust the choice. A correctly sized drive starts the load reliably and runs cool for many years.

Should I size a VFD by kW or by current?

Size it by current, because motors of the same kW can draw quite different currents. Pole count, efficiency and power factor all change the current drawn from the drive.

ABB Technical Guide No 7 advises choosing the drive according to the dimensioning current. The catalogue kW value is only a convenient guide for typical 4 pole motors.

What is the difference between normal duty and heavy duty?

Normal duty allows a small overload, such as 110 percent for 1 minute, and suits pumps and fans. Heavy duty allows a larger overload, such as 150 percent for 1 minute.

Heavy duty suits conveyors, crushers and other constant torque loads. For the same frame, the heavy duty current rating is lower than the normal duty rating.

How much should I derate for altitude?

Many makers derate about 1 percent for every 100 m above 1000 m altitude. ABB states this rule for the ACS580 drive range up to an altitude of 4000 m.

At 2500 m the derate is about 15 percent, so a larger frame may be needed. Always confirm the exact curve published in the manual for your drive.

How does ambient temperature affect the drive?

Most drives are rated for an ambient of 40 °C and lose capacity above that temperature. The Galt G500 manual cited by VFDs.com asks for 1 percent derating per degree above that limit.

Indian panel rooms in summer can easily exceed that temperature limit. Provide good ventilation or air conditioning, or choose a larger drive with enough margin.

Can I run a 3 phase motor on single phase with a VFD?

Yes, many drives accept single phase input with derating, or special single phase input models exist. VFDs.com suggests doubling the motor current as a safe rule.

So a 9 A motor would need a drive rated for 18 A on 3 phase input. Check that the maker permits single phase input for the chosen model.

Why does cable length matter in VFD sizing?

Long motor cables add capacitance, so the drive must supply extra charging current on every switching edge. Reflected waves can also nearly double the voltage seen at the motor terminals.

Check the maximum cable length given in the manual for each frame size. Use an output reactor or a dV/dt filter whenever the cable run exceeds that limit.

Advertisement

Related Articles

External References

What We Learn Today

  • VFD sizing starts from the motor nameplate current, not the kW, because poles, efficiency and power factor change the current a motor draws.
  • Choose normal duty for pumps and fans and heavy duty, often 150 percent for 1 minute, for conveyors, crushers and other constant torque loads.
  • Derate for ambient above 40 °C, altitude above 1000 m, higher switching frequency, long motor cables and single phase supply before ordering the drive.
I hope you like above blog. There is no cost associated in sharing the article in your social media. Thanks for reading!! Happy Learning!!
Author · instrumentationblog.in
Editorial Staff
Instrumentation Blog’s Editorial Staff are industry professionals and technical writers with a strong interest in industrial electrical systems. They specialize in simplifying complex technical concepts into clear, practical, and easy to understand insights. All articles written by the Editorial Staff are technically reviewed before publication.
Technically reviewed on

Leave a Reply

Your email address will not be published. Required fields are marked *