How to Test an RTD: Pt100 Resistance Table & Calculator

Share:
Temperature
How to Test an RTD (Pt100) With a Multimeter and Megger: Resistance Table, 2, 3 and 4 Wire Checks and Fault Finding

A healthy Pt100 gives a predictable resistance at every temperature, so a simple ohm reading tells you a lot about the sensor. This field guide shows the readings to expect, the checks to run on every wire and the faults each reading points to.

Pt100 Table Multimeter Check 3 Wire RTD Lead Resistance Megger Test Fault Finding

Here is how to test an RTD: a Pt100 is checked by isolating it, measuring the element and lead resistances with a multimeter and comparing the result with the standard resistance table. This guide adds the insulation test, a fault table, a calculator and a solved example.

Hello everyone, today we are going to see how to test an RTD in the field with a multimeter and a megger, and how to read the results like an experienced instrument technician.
how to test an RTD

How Do You Test an RTD?

The answer to how to test an RTD is simple: isolate the sensor, measure the resistance between its different coloured wires with a multimeter and compare the value with the Pt100 table at the actual temperature. Then check that same colour wires read close to zero and that the element is well insulated from the sheath, which is how every platinum RTD is proven in the field.

Quick Answer
  • A Pt100 reads 100.00 Ω at 0 °C and 138.51 Ω at 100 °C.
  • At a room temperature of 25 °C, expect about 109.7 Ω between red and white.
  • Same colour wires should read close to 0 Ω, normally well below 1 Ω.
  • An open circuit (OL) means a broken element or lead, a very low reading means a short.
  • Insulation from element to sheath should be at least 100 MΩ.

The resistance rises by about 0.385 Ω per degree Celsius, so even a cheap multimeter can tell a good sensor from a dead one.

Industrial Pt100 RTD probe with a stainless steel sheath and M12 connector, the type of sensor checked with a multimeter
Image credit: DwyerOmega. Image courtesy of DwyerOmega, shown here for educational reference.

DwyerOmega explains that a Pt100 has 100 ohms at 0 °C and a Pt1000 has 1,000 ohms at 0 °C, which is the quickest way to tell the Pt100 and Pt1000 types apart. It adds that a much higher reading usually means the sensor is a thermistor, while a thermocouple shows only a very low loop resistance.

Advertisement

Pt100 Resistance Table for Field Testing

Use the table below to judge your reading. Values follow the IEC 60751 curve for a standard Pt100 with alpha 0.00385, so multiply by 10 for a Pt1000.

TemperaturePt100 resistancePt1000 resistance
minus 100 °C60.26 Ω602.6 Ω
minus 50 °C80.31 Ω803.1 Ω
0 °C100.00 Ω1000.0 Ω
20 °C107.79 Ω1077.9 Ω
25 °C109.73 Ω1097.3 Ω
50 °C119.40 Ω1194.0 Ω
100 °C138.51 Ω1385.1 Ω
150 °C157.33 Ω1573.3 Ω
200 °C175.86 Ω1758.6 Ω
300 °C212.05 Ω2120.5 Ω
400 °C247.09 Ω2470.9 Ω

For any value not in the table, use our RTD resistance to temperature calculator or the calculator further down this page. Remember that the table is for the element alone, so lead resistance must be removed before you compare.

Tools Needed for RTD Testing

  • Digital multimeter with a 200 Ω range and good resolution
  • Insulation tester (megger) set to a low test voltage
  • Reference thermometer or the plant temperature indicator
  • Pt100 resistance table or calculator
  • Screwdriver set and terminal labels
  • Permit to work and loop isolation from the control room
  • Clean cloth and contact cleaner for terminals

How to Test an RTD With a Multimeter in 7 Steps

This is how to check a Pt100 with a multimeter, and the order matters because the first readings decide which later checks are needed. Each step is the same whether the sensor is wired to a temperature transmitter, a PLC card or a panel indicator.

1
Isolate the Loop
Inform operations, put the loop in manual or bypass and disconnect the RTD wires from the transmitter or card terminals.
2
Note the Process Temperature
Read a nearby thermometer or the plant indicator so you know which table value to expect.
3
Identify the Wires
A 3 wire Pt100 usually has one red wire and two white wires, or two of the same colour and one different.
4
Measure Same Colour Pairs
Set the meter to ohms and measure between the two wires of the same colour; this is the lead loop and should be close to zero.
5
Measure the Element
Measure from the different colour wire to each same colour wire; both readings should match the table plus lead resistance.
6
Compare and Correct
Subtract the lead loop reading, convert the result to temperature and compare with the reference reading.
7
Test the Insulation
Join all RTD wires, then test from the wires to the sheath with a low voltage megger before reconnecting.

If the readings look correct, reconnect the wires, restore the loop and watch the value settle. A good sensor that still reads wrong at the DCS usually points to transmitter configuration, such as the wrong sensor type or wire count.

Quick Tip

Always measure at the sensor head first and then at the marshalling cabinet. If the head reading is good and the cabinet reading is not, the fault is in the cable or junction box, not the RTD.

3 Wire RTD Testing and 2 and 4 Wire Checks

The wire count changes what you expect to see, so confirm it before judging any reading. Our guide on 2, 3 and 4 wire RTDs explains why the extra leads exist.

2 Wire RTD

Only two leads, so the meter reads element plus both lead resistances. Long cables add a positive error you cannot separate in the field.

Best for: Short runs and local indicators
2W
3 Wire RTD

One red and two white leads. White to white gives the lead loop, red to either white gives element plus one lead loop.

Best for: Most process plants and transmitters
3W
4 Wire RTD

Two red and two white leads. Same colour pairs read near zero and any red to white pair reads the element.

Best for: Labs, custody transfer and precision loops
4W

The nVent Raychem RTD installation instructions give red to red readings from 0.22 to 21 Ω depending on lead length, and about 107.8 Ω red to white at 20 °C. That spread shows why a long sensor lead must be measured, not assumed.

DwyerOmega gives a neat 3 wire example: red to white read about 110 Ω and white to white read 0.6 Ω, which confirmed a healthy RTD near room temperature. A reading of 110 Ω suggests about 26 °C before lead correction, consistent with the basic RTD curve.

Do You Know?

In a 3 wire circuit, the transmitter subtracts one lead resistance from the other. The method works only when both leads have the same length, size and terminal condition.

Resistance to Temperature Formula With Solved Example

Above 0 °C, IEC 60751 defines the Pt100 curve with the Callendar Van Dusen equation using A = 0.0039083 and B = minus 0.0000005775. Solving the quadratic for T turns any corrected reading into temperature.

Rt = R0 (1 + A·T + B·T²)

Measured red to white = 110.50 Ω
White to white lead loop = 0.60 Ω
Corrected Rt = 110.50 minus 0.60 = 109.90 Ω
T = [minus A + √(A² minus 4B(1 minus Rt/R0))] ÷ 2B
T = 25.43 °C
Reference thermometer = 25.20 °C
Deviation = 0.23 °C
Class B limit at 25 °C = 0.30 + 0.005 × 25 = ±0.43 °C, PASS
RTD Resistance to Temperature Test Calculator
Result
Corrected 109.90 Ω, temperature 25.43 °C, deviation 0.23 °C, Class B limit ±0.43 °C, PASS

The quadratic is exact above 0 °C and close enough down to minus 100 °C; colder work needs the full equation in our Pt100 calibration guide.

Advertisement

Insulation Resistance Test on an RTD

No method for how to test an RTD is complete without an insulation check, because a sensor with correct resistance can still drift if moisture enters the sheath. The nVent Raychem instructions call for a megohmmeter test at no more than 250 V DC, with at least 100 MΩ between the leads and the sheath.

Join all RTD wires together, connect the tester between them and the sheath or ground wire, and never apply the tester across the element itself, since that can damage it. The general method follows our megger test procedure, only at a much lower voltage.

Quick Tip

If the insulation reading is low, warm the sensor head gently and test again. A value that recovers after drying points to moisture at the head or connector rather than inside the sheath.

RTD Fault Finding Table

Knowing how to test an RTD is only half the job; this troubleshooting table turns each reading into a likely cause. Most of these faults also show up as early warning signs on the DCS trend before the sensor fails completely.

ReadingLikely faultField action
OL or open between red and whiteBroken element or lead, loose terminalCheck at the head, then replace the insert
Far below the table value, near 0 ΩShorted element or leadsInspect the cable for crushing, replace the insert
High by a fixed amountLead or terminal resistance, 2 wire errorMeasure the lead loop, clean and tighten terminals
Same colour pair reads several ohmsCorroded or loose lead, wrong pairingRe identify wires, clean terminals
Correct ohms, noisy readingMoisture, low insulation, poor shield earthMegger test, dry the head, check shield
Correct ohms, wrong DCS valueWrong sensor type, wire count or rangeCheck transmitter setup and HART configuration
Reads low in process, fine on benchPoor immersion or air gap in thermowellCheck insertion length and spring loading

An open sensor often drives the output to its burnout value, so a sudden jump to full scale is a clue too.

Do You Know?

A reading that is correct at ambient but wrong in the process often comes from stem conduction. If the insertion depth is too short, heat flows along the sheath and the element sits below the true fluid temperature.

How to Test an RTD Without Removing It

Check the TrendLook for spikes, flat lines or slow drift on the DCS.
Read the TransmitterUse HART to read the sensor ohms and the configured type.
Measure at the CabinetDisconnect and measure resistance from the marshalling side.
Measure at the HeadRepeat at the sensor head to split cable from sensor faults.
Compare With a ReferenceUse a portable thermometer in a test well if one exists.

A smart transmitter often reports raw sensor ohms over HART, which saves a trip to the head for a first check. If you must prove accuracy at more than one point, pull the insert and use a dry block calibrator instead of guessing from ambient readings.

RTD Testing Myths

Myth: If the multimeter shows about 110 Ω, the RTD is accurate.
Fact: A plain multimeter only proves the element is alive. Accuracy needs lead correction and a comparison with a reference temperature.
Myth: Lead resistance does not matter in a 3 wire RTD.
Fact: Compensation works only when both leads match, so a single corroded terminal still adds error.
Myth: A megger at 500 V is the safe default.
Fact: Thin RTD leads and elements can be damaged, so follow the maker limit, such as 250 V DC for the nVent Raychem sensor.
Advertisement

Multimeter Check vs Calibrator Test

When people ask how to test an RTD, they usually mean one of two things: is it alive, or is it accurate. A multimeter answers the first and a calibrator the second; refer to our note on temperature measurement errors when the gap is small.

Multimeter Field Check
  • Fast, cheap and needs no process shutdown beyond isolation.
  • Finds open, short and lead faults within minutes.
  • Works on any 2, 3 or 4 wire sensor.
  • Good first step before calling for a calibration.
Its Limits
  • Meter resolution of 0.1 Ω equals about 0.26 °C.
  • Cannot prove accuracy at temperatures other than ambient.
  • Two wire readings include lead error.
  • Misses intermittent faults caused by vibration or heat.

Raychem RTD Installation Instructions PDF

PDF
Raychem RTD MTO Resistance Temperature Detector Installation Instructions
Maker instructions with lead, element and insulation test values

Video on Checking a 3 Wire RTD

How to Test an RTD FAQ

How to test an RTD and check if it is working?

Disconnect it, measure the resistance between the different coloured wires and compare it with the Pt100 table at the actual temperature. Then confirm that same colour wires read close to zero ohms.

Finish with a low voltage insulation test from the wires to the sheath. A sensor that passes all three checks is healthy, and remaining errors usually sit in the transmitter or wiring.

What should a Pt100 read at room temperature?

A Pt100 reads about 107.8 ohms at 20 degrees and about 109.7 ohms at 25 degrees. Your meter shows a little more because lead resistance adds to the reading.

Measure the lead loop between the same colour wires and subtract it. The corrected value should sit within a few tenths of an ohm of the table figure.

How do you test a 3 wire RTD with a multimeter?

Measure between the two same colour wires first, which gives the lead loop and should read well below one ohm. Then measure from the single colour wire to each of the other two.

Both of those readings should be equal and match the table plus the lead loop. A big difference between them points to a bad lead or a loose terminal on one side.

What resistance does a Pt100 have at 0 degrees?

By definition, a Pt100 has exactly 100 ohms at 0 °C, and a Pt1000 has 1,000 ohms. At 100 °C, the Pt100 reaches about 138.5 ohms on the standard curve.

These two points come from IEC 60751 and give the familiar 0.00385 alpha value. Most industrial sensors used in India follow this curve, so the same table works for most brands.

Can you megger an RTD?

Yes, but only between all wires joined together and the sheath, and at a low test voltage. The nVent Raychem instructions allow a maximum of 250 V DC and expect at least 100 megohms.

Never connect the tester across the element itself, because the voltage can damage it. Disconnect the transmitter first so that its input circuit is not stressed by the test.

Why does my RTD show a very high temperature?

The most common cause is an open element or lead, which pushes many transmitters to an upscale burnout value. A loose terminal, a broken wire or water in the head can do the same.

Measure the resistance at the head and at the cabinet to locate the break. If both read open, the insert itself has failed and needs replacement.

Advertisement

Related Articles

External References

What We Learn Today

  • Knowing how to test an RTD starts with the Pt100 table: 100 Ω at 0 °C, 138.51 Ω at 100 °C and about 0.385 Ω per degree.
  • Same colour lead pairs should read close to zero, and the lead loop must be subtracted before you convert a reading to temperature.
  • A low voltage insulation test from all wires to the sheath, at least 100 MΩ, catches the moisture faults that ohm readings miss.
I hope you like above blog. There is no cost associated in sharing the article in your social media. Thanks for reading!! Happy Learning!!
Sunayana Gadepatil, author at Instrumentation Blog
Author · instrumentationblog.in
Ms. Sunayana Gadepatil is an instrumentation professional, technical writer, and the author behind Instrumentation Blog. With a strong interest in industrial instrumentation, process measurement, and automation, she specializes in simplifying complex technical concepts into clear, practical, and easy to understand insights. Through her articles, Ms. Sunayana shares valuable knowledge on flow, pressure, level, temperature, control systems, and industrial automation for engineers, students, technicians, and industry professionals.
Technically reviewed on

Leave a Reply

Your email address will not be published. Required fields are marked *