Equipotential Bonding: 7 Essential Rules for Safer Plants

Share:
Electrical Safety & Standards
Equipotential Bonding: 7 Essential Rules for Safer Plants

A person touching a water pipe and a faulty appliance at the same time can be exposed to a dangerous voltage difference, even when the earthing looks perfect. Good bonding joins all touchable metalwork so that difference stays too small to hurt anyone.

Main Bonding Supplementary Bonding Extraneous Parts IEC 60364 Continuity Tests

Earthing gives fault current a path, but it does not by itself keep nearby metal parts at the same voltage. Equipotential bonding closes that gap by joining pipes, steelwork and equipment frames with properly sized conductors.

Hello everyone, today we are going to learn what equipotential bonding is, how main and supplementary bonding conductors are sized and tested, and where IEC 60364 and IS 732 demand them.
equipotential bonding

What Is Equipotential Bonding?

Equipotential bonding is the practice of connecting all exposed conductive parts and extraneous conductive parts in an installation with low resistance conductors, so that they rise and fall in voltage together during a fault. It works alongside the earthing arrangement described in TN, TT and IT earthing systems, and it is the main reason touch voltages stay safe while a protective device clears the fault.

An exposed conductive part is the metal body of equipment, such as a motor frame, which becomes live only under fault. An extraneous conductive part is metal outside the installation that can introduce a potential, such as a water pipe, gas line or structural steel.

equipotential-busbars-with-terminal-block-system
Image credit: Electrical Engineering Portal. Photo courtesy of Electrical Engineering Portal, shown here for educational reference.

The photo shows an equipotential busbar, where bonding conductors from services and steelwork meet the main earthing terminal. Without it, a fault can leave a pipe at a very different voltage from the frame beside it, a classic cause of electric shock in plant rooms.

Advertisement

Why Bonding Matters Even With Good Earthing

When a phase conductor touches a metal enclosure, fault current flows through the protective conductor and develops a voltage across it. A good earth electrode, sized as shown in earthing resistance calculation, does not remove this voltage, it only sets how much current flows back to the source.

If a nearby water pipe is still at true earth potential, a person holding both the pipe and the enclosure sees the full voltage drop on the protective conductor. Equipotential bonding pulls the pipe up to the same voltage as the frame, so the hand to hand voltage becomes small.

6 mm²Minimum copper main bonding conductor
25 mm²Copper size need not exceed
50 VTouch voltage limit in IEC 60364 4 41
600 mmBond within this distance of a meter
Do You Know?

Substation earth grids use the same idea on a larger scale, with a buried mesh acting as equipotential bonding for the whole switchyard. IEEE 80 calls the resulting limits step and touch voltage.

Types of Equipotential Bonding in an Installation

Main Protective Bonding

Joins incoming metal services and building steel to the main earthing terminal near their point of entry.

Best for: every building and plant substation
Mandatory
Supplementary Bonding

Joins exposed and extraneous parts that can be touched together in one location.

Best for: bathrooms, plant rooms and pump houses
Local
Functional Bonding

Provides a clean reference for electronics, screens and signal circuits.

Best for: control rooms and instrument panels
Signal
Lightning and Static Bonding

Joins metal parts to stop flashover and spark discharge.

Best for: tank farms, roof steel and hazardous areas
Protective

Main and supplementary equipotential bonding protect people from shock. Functional bonding for instruments follows the rules in grounding techniques and earthing in process plants, yet all of them meet at one earthing system.

IEC, IS and BS Rules for Equipotential Bonding

StandardWhat It CoversKey Requirement
IEC 60364 4 41Protection against electric shockMain bonding in every building, supplementary bonding where disconnection is not fast enough
IEC 60364 5 54Earthing arrangements and protective conductorsConductor sizes for main and supplementary bonding
IS 732Indian code for wiring installationsFollows the IEC 60364 approach for bonding
IS 3043Indian code of practice for earthingEarth electrodes, earthing conductors and bonding of metalwork
BS 7671UK wiring regulationsClause 544 for bonding sizes and connection points
IEC 60079 14Electrical installations in hazardous areasPotential equalisation of all exposed and extraneous parts
Quick Tip

Before you size anything, ask which earthing system the site uses, because the bonding conductor size is linked to the main earthing conductor. A TN C S supply in a city building and a TT supply on a remote pump site lead to different numbers.

Equipotential Bonding Conductor Sizes and Formula

Electrical Engineering Portal, quoting IEC 60364 5 54, gives 6 mm² copper as the minimum main bonding conductor and notes that copper need not exceed 25 mm². The same article lists 2.5 mm² copper for supplementary bonding with mechanical protection and 4 mm² copper without it.

IEC 60364 5 54 also requires the main bonding conductor to be at least half the cross section of the largest protective earthing conductor, with 16 mm² aluminium or 50 mm² steel as alternatives to 6 mm² copper. For the effectiveness of supplementary equipotential bonding, IEC 60364 4 41 gives the resistance check shown below.

Main bonding size S ≥ 0.5 × S earthing conductor, minimum 6 mm² copper, need not exceed 25 mm² copper
Supplementary bonding: R ≤ 50 V ÷ Ia for AC, R ≤ 120 V ÷ Ia for DC

Ia is the current that operates the protective device in the required time

Example: 32 A Type B MCB, magnetic trip at 5 × In
Ia = 5 × 32 = 160 A
R ≤ 50 ÷ 160 = 0.313 Ω

For a circuit breaker, Ia is the instantaneous trip current, which is 5 times the rating for Type B, 10 times for Type C and 20 times for Type D, as explained in MCB, MCCB, ELCB and RCCB. For an RCD, Ia is simply the rated residual current, so the allowed resistance becomes very large.

Supplementary Bonding Resistance Calculator

Maximum Resistance of a Supplementary Bond
Result
Ia = 160.0 A, maximum bond resistance 0.313 ohm
Advertisement

Second Worked Example: RCD Protected Bathroom Circuit

Take a geyser circuit in a hotel bathroom protected by a 30 mA RCD, so Ia is 0.03 A. The limit becomes R ≤ 50 ÷ 0.03 = 1666.7 Ω, which any copper bond meets easily.

This is why codes relax supplementary equipotential bonding when every circuit in a wet room has 30 mA protection, unlike breaker circuits sized as in how to calculate MCB rating. The RCD then does most of the protective work.

7 Essential Rules for Equipotential Bonding

1
Bond at the Entry Point
Connect water, gas, oil and other metal services as close as practicable to where they enter.
2
Bond Structural Steel
Join building steel, cable trays and metal ducts that are extraneous parts.
3
Size From the Earthing Conductor
Use at least half its size, never below 6 mm² copper.
4
Use Proper Clamps
Fit bonding clamps rated for the pipe size and material, never wrapped wire.
5
Keep Bonds Continuous
Run conductors unbroken from the clamp to the main earthing terminal.
6
Label Every Connection
Fix a safety label reading Safety Electrical Connection, Do Not Remove at each clamp.
7
Test and Record
Measure continuity and record the resistance on the test certificate.

Professional Electrician magazine, discussing BS 7671 clause 544.1.2, notes that main bonding should be made as near as practicable to the point of entry and, where practicable, within 600 mm of the meter outlet union. That keeps the full length of the service on the consumer side at the bonded potential.

Protective conductors are sized by the adiabatic method in earth conductor size calculation, using the fault level from short circuit current calculation. Equipotential bonding sizes then follow from that earthing conductor.

Bathrooms, Pools and Other Special Locations

Bathrooms carry a higher shock risk because wet skin has low resistance and people touch taps and pipes. The IET Wiring Matters article on equipotential bonding shows a bathroom where metal pipes and equipment are bonded together locally.

BS 7671 allows supplementary bonding in a bathroom to be omitted only when all circuits in the room have 30 mA RCD protection, meet the disconnection times and the building already has main bonding. Swimming pools, saunas, agricultural sheds and medical rooms have their own part 7 rules, and many still demand a local bonding grid.

Do You Know?

Plastic water pipes do not need bonding, but a short metal section joined by plastic pipe at both ends is usually not an extraneous part. Bonding such isolated metal can even import a fault voltage into an area where it was not present.

Equipotential Bonding in Hazardous Areas and for Static

In plants with flammable gases or dust, IEC 60079 14 requires potential equalisation, which means every exposed and extraneous part is connected into the equipotential bonding system. The zone concept behind this is covered in hazardous area classification.

Mark Coles, writing in IET Wiring Matters, notes that resistance between well contacted metal parts is typically only a few ohms. A metal part needs a resistance to earth above 1 MΩ to hold a significant static charge, so normal bonding drains it easily.

Quick Tip

On flanged pipe runs in tank farms, check whether flange bolts give metal to metal contact before adding jumpers. Painted or gasketed flanges with insulating kits need a bonding strap across them unless the insulation is intentional for cathodic protection.

Testing Equipotential Bonding on Site

  • Isolate the supply and prove dead before disconnecting any bond.
  • Null the test leads of the low resistance ohmmeter.
  • Measure from the main earthing terminal to each service clamp.
  • Compare readings with the design limit or the R ≤ 50 V ÷ Ia value.
  • Check clamps are tight, clean and correctly labelled.
  • Confirm the bond is on the consumer side of meters and insulating joints.
  • Record every reading on the installation test certificate.

Continuity of equipotential bonding is normally measured with the low resistance range of a multifunction tester at around 200 mA test current. It is a separate test from the insulation resistance test with a megger, which checks that conductors are not leaking to earth.

Electrical Engineering Portal mentions a guide value of less than 1 Ω as sufficient for connections in equipotential bonding. Loop impedance at the far end of a circuit, covered in earth fault loop impedance testing, confirms that the protective device will actually trip in time.

Myth: Good earthing makes bonding unnecessary.
Fact: Earthing sets the fault current, while equipotential bonding limits the voltage between parts a person can touch.
Myth: Every metal object must be bonded.
Fact: Only extraneous parts that can introduce a potential need bonding, small isolated metal items do not.
Myth: Thicker bonding wire is always better.
Fact: Above 25 mm² copper there is little gain for main bonding, and a good clamp matters more.
Myth: Bonding and earthing mean the same thing.
Fact: Earthing connects to the ground, bonding connects parts to each other, and both meet at the main earthing terminal.

Benefits and Practical Limits

Advantages of Equipotential Bonding
  • Keeps touch voltage low during earth faults.
  • Reduces risk of sparks between metal parts in hazardous areas.
  • Drains static charge from pipes and vessels.
  • Helps lightning protection by preventing side flashes.
Limitations
  • Does not replace fast fault disconnection.
  • Clamps loosen and corrode over time.
  • Later plastic pipe changes can break the bond path.
  • Poor routing can create loops that pick up noise.
Advertisement

Where Equipotential Bonding Is Applied

Plant Substations
Cable trays, doors, fences and steel columns tied to the earth grid.
Pump Houses
Pipes, valves and motor frames bonded at the pump skid.
Tank Farms
Tanks, loading arms and road tanker connections for static control.
Bathrooms and Kitchens
Taps, metal pipes and appliance frames in wet areas.
Control Rooms
Raised floor pedestals, cabinets and cable screens.
Rooftop Solar
Module frames and mounting structures joined to the earthing system.

IET Earthing and Bonding in Hazardous Locations PDF

PDF
Earthing and Bonding in Hazardous Locations
IET Wiring Matters technical article by Mark Coles

Main Protective Bonding Video

Equipotential Bonding FAQ

What is equipotential bonding in simple words?

It means joining all the metal parts a person can touch with copper conductors so they stay at nearly the same voltage. If a fault makes one part live, the others rise with it.

Because the difference between them stays small, very little current can pass through a body touching both. Fast disconnection by the protective device then clears the fault safely.

What is the difference between main and supplementary bonding?

Main bonding connects incoming services such as water and gas pipes and building steel to the main earthing terminal. It is made near the point where each service enters the premises.

Supplementary bonding is local and joins parts that can be touched together within one room or area. It is used where shock risk is high or where disconnection may be too slow.

What size should a main bonding conductor be?

Under IEC 60364 5 54 it must be at least half the size of the main earthing conductor. The minimum is 6 mm² copper and it need not exceed 25 mm² in copper.

Aluminium and steel conductors are allowed with larger minimum sizes of 16 and 50 square millimetres. Always follow the local supply authority and the project specification as well.

How do you check if supplementary bonding is effective?

Measure the resistance between the two parts with a low resistance ohmmeter. Then compare it with 50 volts divided by the current that trips the protective device.

For a 32 A Type B breaker, the trip current is 160 amps and the limit works out near 0.31 ohm. With a 30 mA RCD the limit rises to about 1667 ohms.

Is bonding needed in a bathroom with plastic pipes?

Plastic pipes are not conductive, so they do not need bonding themselves. Short metal sections joined only by plastic pipe are normally not extraneous parts either.

Supplementary bonding may be omitted in many cases if all circuits in the room have 30 mA RCD protection. The main bonding of the whole building must still be present, correctly sized and tested.

Why is equipotential bonding important in hazardous areas?

A voltage difference between two metal parts can produce a spark that ignites gas or dust. Bonding removes that difference and also drains static charge from pipes and vessels.

IEC 60079 14 therefore requires potential equalisation of all exposed and extraneous parts. Flanges, road tanker connections, hoses and loading arms are the usual points that need regular checks.

How often should equipotential bonding be tested?

It should be tested at commissioning and then at every periodic inspection of the installation. Many plants also repeat the test after any pipework, tank or structural modification.

Industrial sites in coastal or humid regions of India often test yearly, since clamps corrode faster there. Record each reading on the certificate so that slowly rising values are noticed early.

Advertisement

Related Articles

External References

What We Learn Today

  • Equipotential bonding joins exposed and extraneous conductive parts so that touch voltages stay small while the protective device clears an earth fault.
  • Main bonding conductors need at least half the earthing conductor size, with a 6 mm² copper minimum, and need not exceed 25 mm² in copper.
  • Supplementary bonds are effective when their resistance is at most 50 V divided by Ia, so a 32 A Type B breaker allows about 0.313 Ω.
I hope you like above blog. There is no cost associated in sharing the article in your social media. Thanks for reading!! Happy Learning!!
Author · instrumentationblog.in
Editorial Staff
Instrumentation Blog’s Editorial Staff are industry professionals and technical writers with a strong interest in industrial electrical systems. They specialize in simplifying complex technical concepts into clear, practical, and easy to understand insights. All articles written by the Editorial Staff are technically reviewed before publication.
Technically reviewed on

Leave a Reply

Your email address will not be published. Required fields are marked *