Motor Protection Relay Types: Overload, Short Circuit and Earth Fault

Share:
Electrical Fundamentals
Motor Protection Relay Types: Overload, Short Circuit and Earth Fault

A motor protection relay detects abnormal conditions and trips the contactor before damage occurs. Four functions cover the most common failure modes: thermal overload, short circuit, earth fault, and phase loss.

This guide explains how each protection function works, the settings formulas, and how to configure a complete motor protection scheme for any three-phase induction motor.

Thermal Overload Short Circuit (ANSI 50) Earth Fault (ANSI 51N) Phase Loss Trip Time Curve
Hello everyone, today we are going to learn about motor protection relay types. We will understand what each protection function does, how to set the pickup current and trip time for overload, short circuit, and earth fault protection, and how to select the right relay type for a given motor application.

A motor without protection is running on borrowed time. The most common failure modes are all detectable: thermal overload, short circuit, earth fault from insulation failure, and single-phasing from a blown fuse.

A correctly configured motor protection relay catches all four.

motor protection relay

The 4 Motor Protection Functions Every Engineer Should Know

Thermal Overload Protection (ANSI 49)
Pickup: 105 to 125% FLC. Trip class: 10, 20, 30

Detects sustained overcurrent that exceeds the motor's thermal capacity. The relay integrates the I²t heating over time using the thermal image model. Trip time decreases as the overload multiple increases.

Protects against: mechanical overload (seized bearing, jammed pump), supply voltage dip causing high current draw, slow acceleration due to high load inertia.

Short Circuit Protection (ANSI 50)
Pickup: 800 to 1200% FLC. Instantaneous trip

Detects phase-to-phase or three-phase short circuit current. The pickup must be set above the motor starting current peak (typically 600 to 700% FLC) to avoid nuisance tripping during direct-on-line starting.

Protects against: winding insulation failure, cable fault between motor and switchgear, phase-to-phase fault at motor terminals.

Earth Fault Protection (ANSI 51N)
Pickup: 5 to 20% FLC. Time delay: 0.1 to 0.5 s

Detects current flowing from a phase conductor to earth through degraded insulation or a direct fault. Measured using the residual current method (sum of three-phase currents) or a dedicated core balance CT.

Protects against: insulation breakdown, moisture ingress, cable damage, bearing current damage to motor frame.

Phase Loss Protection (ANSI 46)
Detection: current unbalance above 15 to 20%

Detects the loss of one supply phase. Single-phasing causes the motor to draw 150 to 200% of FLC on the two remaining phases, rapidly overheating the windings.

A standard thermal overload relay detects single-phasing only if the motor is loaded above about 75% of full load.

Protects against: blown fuse on one phase, open contact on one pole of the contactor, supply cable open circuit.

Advertisement

Motor Protection Relay: How Each Function Connects

SUPPLY 3-phase MCCB Short circuit 3x CT Ia Ib Ic CONTACTOR Trip coil MOTOR 3-phase induction Earth/PE CT sec. MOTOR PROTECTION RELAY 49: Overload 50: Short Cct 51N: Earth Flt 46: Phase Loss Trip MCCB: ANSI 50 short circuit CTs: current measurement Relay: ANSI 49, 51N, 46 protection Trip signal to contactor coil CT secondary wiring
Did You Know? Most modern motor protection relays use a thermal image model (also called a thermal replica or I²t model) rather than a simple current threshold. The thermal image integrates the motor winding temperature based on the measured current squared over time, factoring in the motor's thermal time constant. The relay can also account for the motor's previous thermal state, so a motor that has already been running warm trips faster on the next overload than one starting from cold.

This prevents a motor from being restarted immediately after an overload trip, which would force the already-hot windings to absorb even more heat during the next starting transient. The thermal image model is defined in IEC 60255-149.

How to Set Each Protection Function

Overload Protection Setting (ANSI 49)

The overload pickup current (Ip) is set based on the motor full-load current (FLC) from the nameplate. The standard setting range is 100 to 125 percent of FLC. For most applications, set Ip = 100 to 105 percent of FLC to provide the tightest protection without nuisance tripping.

The trip class is the maximum trip time at 6x pickup current. Class 10 trips in 10 s, Class 20 in 20 s, Class 30 in 30 s.

Use Class 10 for standard motors. Use Class 20 or Class 30 for high-inertia motors (large fans, compressors, ball mills).

Overload multiple
Approximate trip time range (Class 10 to Class 30)
Meaning
1.05x FLC
Does not trip (within continuous rating)
No trip
1.2x FLC
Very long delay thermal protection accumulates slowly
Minutes
2x FLC
Class 10: 60 to 120 s. Class 20: 120 to 240 s. Class 30: 200 to 360 s
1 to 6 min
6x FLC
Class 10: 10 s. Class 20: 20 s. Class 30: 30 s (class definition point)
10 to 30 s
10x FLC
Near-instantaneous trip. Thermal model saturates quickly.
Under 4 s

Short Circuit Setting (ANSI 50)

The short circuit instantaneous pickup (Is) must be set above the motor starting current peak and below the minimum fault current at the motor terminals. The standard formula is:

Is = 8 to 12 x FLC (typical)
Must be above DOL starting peak (6 to 7x FLC) and below minimum two-phase fault current

For soft-starter or VFD-fed motors, the starting current is limited. The short circuit pickup can be set lower, at 4 to 6x FLC.

Always verify that the minimum calculated fault current at the motor terminals exceeds the pickup by at least 20 percent margin.

Earth Fault Setting (ANSI 51N)

The earth fault pickup (Ie) is typically 5 to 20 percent of FLC. A lower pickup detects insulation faults earlier but can cause nuisance tripping from zero-sequence imbalance in long cable runs.

For high-resistance earthing systems (IT or high-resistance neutral), the earth fault pickup must be calculated from the system earth fault current level. See the earthing resistance calculation guide for the formula.

Advertisement

Motor Protection Relay Setting Calculator

Motor Protection Settings Calculator
Enter motor nameplate data to calculate recommended relay settings
Motor full-load current (FLC)--
Overload pickup Ip (set at 105% FLC)--
Recommended trip class--
Short circuit pickup Is--
Earth fault pickup Ie (10% FLC)--
Phase loss detection threshold--

Worked Example: 11 kW Motor, 400 V, DOL Start

Motor protection settings 11 kW, 400 V, DOL, efficiency 88%, power factor 0.85
Step 1: Full-load current (FLC)
FLC = P / (sqrt(3) x V x eta x PF)
FLC = 11000 / (1.732 x 400 x 0.88 x 0.85) = 11000 / 515.8 = 21.3 A

Step 2: Overload protection (ANSI 49)
Pickup Ip = 1.05 x FLC = 1.05 x 21.3 = 22.4 A
Trip class: Class 10 (standard pump, low inertia)
Reset: automatic after thermal image cools to 100% (typically 5 to 15 min)

Step 3: Short circuit protection (ANSI 50)
DOL starting peak = approximately 6x FLC = 6 x 21.3 = 127.8 A
Short circuit pickup Is = 10 x FLC = 10 x 21.3 = 213 A
Verify: Is (213 A) is above DOL peak (128 A) and below min fault current at motor terminals

Step 4: Earth fault protection (ANSI 51N)
Earth fault pickup Ie = 10% x FLC = 0.10 x 21.3 = 2.13 A
Time delay: 0.2 s (to ride through transient zero-sequence current on starting)

Step 5: Phase loss protection (ANSI 46)
Set current unbalance threshold to 15%
Time delay: 2 to 5 s (to ride through momentary voltage unbalance on the network)

Correct vs Incorrect Motor Protection Relay Selection

Correct Selection and Configuration
  • Overload pickup set at 100 to 105% of motor FLC from nameplate
  • Trip class matched to starting inertia (Class 10 for pumps, Class 20 to 30 for compressors)
  • Short circuit pickup above DOL peak (128% x FLC) and below minimum fault current
  • Earth fault pickup at 5 to 10% FLC with short time delay (0.1 to 0.5 s)
  • Phase loss detection enabled with 15 to 20% unbalance threshold
  • CT ratio correctly matched so secondary current at FLC is within relay input range
  • Protection relay tested with secondary injection before commissioning
Common Configuration Mistakes
  • Overload pickup set too high (e.g. 130 to 150% FLC) to stop nuisance trips this removes thermal protection
  • Wrong trip class (Class 10 on a compressor) causes nuisance trips during every start
  • Short circuit pickup set below DOL starting peak relay trips on every motor start
  • Earth fault disabled or set too high insulation damage goes undetected until complete failure
  • Phase loss protection not enabled motor destroyed by single-phasing before thermal relay trips
  • CT ratio wrong relay reads 50% of actual current and never trips on overload
  • Relay not tested settings incorrect but fault not discovered until first motor failure
Tip: Always test motor protection relay settings using secondary injection before commissioning.

Secondary injection means applying a test current directly to the relay current input terminals, bypassing the CTs and the actual motor circuit. This verifies that the relay trips at the correct current and time without needing to force an actual fault condition. A relay with wrong CT polarity wiring will not detect earth faults even if the pickup and time settings are correct. Secondary injection catches wiring errors that parameter verification alone cannot find.

Watch: Motor Protection Relay Setup and Testing

Advertisement

Motor Protection Relay Questions Engineers Ask

What is the difference between ANSI 49 and ANSI 50 motor protection?
ANSI 49 is thermal overload protection that trips after sustained overcurrent heats the winding. ANSI 50 trips instantly when current exceeds 8 to 12x FLC, indicating a winding or cable fault.
What is a motor protection relay trip class?
Trip class defines the trip time at 6x pickup current. Class 10 trips in 10 s, Class 20 in 20 s, Class 30 in 30 s. Use Class 10 for most motors.
How is earth fault protection different from overload protection?
Overload protection responds to sustained overcurrent in each phase. Earth fault protection measures the residual current (sum of three phase currents), which is zero when healthy and rises when leakage occurs.
Why does a motor protection relay have a short time delay on earth fault?
A short delay of 0.1 to 0.5 seconds prevents nuisance tripping from momentary zero-sequence imbalance during motor starting or from capacitive charging current in long cable runs.
Can a standard thermal overload relay detect single-phasing?
Only partially. A standard thermal relay detects single-phasing above 75% motor load. Below this, the current on the remaining phases may not exceed the overload pickup. A phase loss relay is required.

Related Articles on This Site

External References

Advertisement

What We Learn Today

  • Four functions protect a three-phase motor: ANSI 49 thermal overload (pickup at 105% FLC, Class 10 to 30), ANSI 50 instantaneous short circuit (pickup at 8 to 12x FLC), ANSI 51N earth fault (pickup at 5 to 10% FLC, 0.1 to 0.5 s delay), and ANSI 46 phase loss (15 to 20% current unbalance threshold).
  • The short circuit pickup must be above the DOL starting peak (approximately 6 to 7x FLC) and below the minimum fault current at the motor terminals. For VFD or soft-starter fed motors, the starting current is limited and the short circuit pickup can be set lower at 4 to 6x FLC.
  • A standard thermal overload relay does not reliably detect single-phasing below 75% motor load. A dedicated phase loss or current unbalance protection function (ANSI 46) is required to detect single-phasing at all load levels and protect the motor windings before they overheat.
I hope you like above blog. There is no cost associated in sharing the article in your social media. Thanks for reading!! Happy Learning!!

Leave a Reply

Your email address will not be published. Required fields are marked *