Surge Arrester: 5 Powerful Selection Rules for Safe Grids

Share:
Power Quality & Protection
Surge Arrester: 5 Powerful Selection Rules for Safe Grids

A column of zinc oxide blocks that behaves like an open circuit at normal voltage and a short path to earth during a surge.

Metal Oxide Arrester MCOV Protective Margin Lightning Protection

A surge arrester limits lightning and switching overvoltages by conducting surge current to earth and then returning to a high resistance state. It protects the insulation of transformers, cables and switchgear.

Hello everyone, today we are going to learn how a surge arrester works, how to select its voltage and current ratings, and why installation details like lead length matter so much.
surge arrester

What Is a Surge Arrester?

A surge arrester is a protective device connected between a live conductor and earth that clamps overvoltages to a safe level. Modern units use zinc oxide blocks, a much larger cousin of the varistor.

At normal system voltage, the zinc oxide blocks conduct only a tiny leakage current. When a surge arrives, their resistance collapses and they carry thousands of amps to earth.

Polymer housed metal oxide surge arresters for distribution networks
Image credit: CHINT

Once the surge passes, the blocks return to high resistance without interrupting the system. Older gapped silicon carbide designs have largely been replaced by gapless metal oxide units.

CHINT explains that the term lightning arrester often refers to outdoor devices on lines and poles. In practice, both names describe the same voltage limiting principle.

How the Arrester Clamps a Surge

Surge ArrivesLightning or switching overvoltage travels along the line
Blocks ConductZinc oxide resistance drops sharply
Current to EarthSurge current flows through the arrester
Voltage ClampedResidual voltage stays below insulation level
RecoveryBlocks return to high resistance

The voltage left across the arrester during discharge is called the residual voltage or protective level. It must be comfortably below the basic insulation level, or BIL, of the protected equipment.

A low resistance earth connection is essential, since surge current must reach the ground quickly. Follow the practices in earthing resistance calculation for the arrester earth.

5 Powerful Surge Arrester Selection Rules

1
Continuous Voltage
MCOV must exceed the highest continuous phase to earth voltage.
2
Temporary Overvoltage
Rated voltage must withstand earth fault TOVs for their duration.
3
Discharge Class
Choose nominal discharge current, such as 5, 10 or 20 kA.
4
Protective Margin
Residual voltage must sit well below equipment BIL.
5
Location and Leads
Mount close to the equipment with short, straight leads.

Rule 2 depends on neutral earthing. On isolated or resistance earthed systems, healthy phases rise close to line voltage during an earth fault, so the arrester needs a higher rating.

Neutral earthing choices are covered in neutral grounding resistor sizing and in TN, TT and IT earthing systems.

Protective Margin and Lead Length Formula

Lead voltage = L × di/dt
Protective margin = (BIL ÷ Voltage at equipment minus 1) × 100

Worked example, 11 kV transformer:
BIL = 95 kV, arrester residual voltage = 30 kV
Lead length 1.5 m at about 1 µH per m, di/dt = 10 kA per µs
Lead voltage = 1.5 µH × 10 kA per µs = 15 kV
Voltage at equipment = 30 + 15 = 45 kV
Protective margin = (95 ÷ 45 minus 1) × 100 ≈ 111 percent

The lead voltage adds directly to the residual voltage seen by the equipment. Long, looping leads can cut the protective margin in half, so keep connections short and straight.

Guides such as the Hubbell application guide recommend keeping a healthy margin for lightning surges. Distance between the arrester and the protected equipment also raises voltage through travelling wave reflections.

MCOV Selection by Earthing Type

System EarthingEarth Fault Voltage on Healthy PhasesMCOV Guidance
Solidly earthedClose to phase to earth voltageAt least phase to earth voltage
Resistance earthedNear line voltage for fault durationHigher rating for TOV
Isolated neutralLine voltage, possibly for hoursRating near full line voltage
Example 11 kV solidMax 12 kV, so 6.93 kV to earthMCOV at least 6.93 kV

For an 11 kV solidly earthed system, the highest system voltage is about 12 kV, so the phase to earth value is 12 divided by the square root of 3. That gives 6.93 kV as the minimum MCOV.

Choosing too low an MCOV leads to overheating and failure. Choosing far too high reduces protection, so balance both sides carefully.

Where a Surge Arrester Is Installed

Transformer Terminals
Protecting windings from lightning on overhead lines.
Cable Terminations
Where overhead lines meet underground cables.
Substation Entrances
Line entry points into switchyards.
Motor Terminals
Large HV motors fed by long cables.
Capacitor Banks
Limiting switching overvoltages.
LV Panels
Surge protective devices for electronics.

At low voltage, the equivalent device is the SPD, selected using IEC 61643 SPD selection rules. Coordinated protection uses arresters at MV and SPDs at LV.

For sensitive electronics, see our guide to surge protector types, which covers Type 1, 2 and 3 devices.

Protective Margin Calculator

Voltage at Equipment and Margin
Result
Voltage at equipment 45.0 kV, margin 111 percent

The calculator assumes about 1 µH per metre of lead. Try 4 m of lead to see how quickly the margin shrinks.

Advantages
  • Clamps lightning and switching surges.
  • No interruption of service.
  • Gapless metal oxide design is reliable.
  • Protects expensive transformers and cables.
Watch Points
  • Wrong MCOV causes overheating.
  • Long leads reduce protection.
  • Poor earthing defeats the arrester.
  • Failed units need prompt replacement.

Metal Oxide Surge Arrester Application Guide

PDF
Metal Oxide Surge Arrester Guide for AC Systems
Hubbell application guide on ratings, TOV and protective margins

Surge Arrester Working Video

Surge Arrester FAQ

What does a surge arrester do?
It clamps overvoltages by diverting surge current to earth.
What is MCOV?
Maximum continuous operating voltage the arrester can withstand indefinitely.
What is residual voltage?
The voltage across the arrester while it discharges surge current.
Why keep leads short?
Lead inductance adds voltage and reduces protection.
Is a lightning arrester different?
The term usually refers to outdoor line arresters using the same principle.
What material is used?
Zinc oxide blocks in gapless designs.
Where should it be mounted?
As close as possible to the equipment it protects.

Related Articles

External References

What We Learn Today

  • Zinc oxide blocks clamp surges and recover without interrupting service.
  • MCOV and rated voltage depend on system earthing and temporary overvoltages.
  • Short leads and close mounting preserve the protective margin.
I hope you like above blog. There is no cost associated in sharing the article in your social media. Thanks for reading!! Happy Learning!!

Leave a Reply

Your email address will not be published. Required fields are marked *