Instrument Air Consumption: 7 Simple Steps for Smooth Sizing

Share:
Design
Instrument Air Consumption: 7 Simple Steps for Smooth Sizing

Every positioner, converter and on off actuator in a plant draws a little air, and together they decide the size of the compressor, dryer, receiver and header. Getting the total right keeps valves responsive and avoids a costly shortage after start up.

Positioner Bleed Stroking Demand Receiver Sizing ISA 7.0.01

Control valves stop moving when the air header collapses, so the air system must be sized from a careful demand estimate. This guide shows how to build an instrument air consumption figure and turn it into compressor, receiver and header sizes.

Hello everyone, today we are going to learn how to calculate instrument air consumption for a plant, and how that figure sizes the compressor, dryer, receiver and air header.
instrument air consumption

What Is Instrument Air Consumption?

Instrument air consumption is the total flow of clean, dry compressed air needed by all pneumatic instruments and actuators in a plant, usually expressed in Nm³/h or scfm. It includes the steady bleed of positioners and converters, the air used each time a valve strokes, purges, and an allowance for leaks and growth.

Most of this air feeds control valves through a valve positioner, so the valve list is the starting point of the calculation. On off valves with solenoid valves add short bursts of demand each time they open or close.

P and ID of an instrument air system with compressor, refrigerated dryer, filters and receiver
Image credit: Compressed Air Best Practices. Diagram courtesy of Compressed Air Best Practices, shown here for educational reference.

The sketch above shows the usual chain of compressor, aftercooler, receiver, dryer and filters before the air reaches the plant header. Each of these items is sized from the same demand figure, so an error at the start spreads through the whole design.

Advertisement

Where the Air Goes in a Process Plant

Positioner Steady Bleed

Pilot relays bleed a small flow all the time, even when the valve is still.

Best for: every modulating control valve
Continuous
I/P Converters

Flapper nozzle converters also bleed continuously.

Best for: older or separate I/P loops
Continuous
Stroking Demand

Air to fill the actuator each time it moves.

Best for: on off valves and large changes
Intermittent
Purges and Bubblers

Small steady flows for level bubblers and analyzer or panel purges.

Best for: tanks, analyzer houses
Continuous
Dryer Purge Loss

Desiccant dryers use part of the dried air to regenerate.

Best for: desiccant dryers
Loss

Sebesta Blomberg engineer Bruce Bullough gives examples from manufacturer data: one I/P converter needed 1.02 Nm³/h (0.60 scfm) and another 0.59 Nm³/h (0.35 scfm). A valve positioner bled 1.21 Nm³/h (0.71 scfm) at steady state but used 21.4 Nm³/h (12.6 scfm) while adjusting position.

1.21 Nm³/hPositioner steady bleed, Bullough example
21.4 Nm³/hSame positioner while moving
6 barTypical plant air pressure
15 to 20 %Desiccant dryer purge loss

Modern low bleed digital positioners use much less air than older designs, so always take figures from the actual datasheet. Power Engineering notes that desiccant dryer purge air consumes about 15 to 20 percent of compressor capacity, a loss that must be added on top of the instrument air consumption.

Do You Know?

A positioner can use more than ten times its steady bleed while it is moving the valve, as Bullough shows with 1.21 Nm³/h at rest and 21.4 Nm³/h during adjustment. This is why a header sized only on steady bleed can sag during a plant upset.

Air Quality Required by ISA 7.0.01

ParameterISA 7.0.01 RequirementWhy It Matters
Pressure dew pointAt least 10 °C below the lowest ambient, never above 4 °C at line pressureStops water and ice in tubing
Particle sizeMaximum 40 micrometresProtects nozzles and relays
Oil contentMaximum 1 ppm w/w, liquid and vapourPrevents gummy deposits
ContaminantsFree of corrosive, flammable or toxic gasesProtects people and parts

Compressed Air Best Practices summarises these four limits of ISA 7.0.01, and Bullough adds that many plants specify a dew point of minus 40 °C, rarely higher than minus 20 °C. The risks of wet air are explained in dew point in instrument air and water vapour in instrument air lines.

How to Calculate Instrument Air Consumption in 7 Steps

1
List Every Consumer
Use the instrument index and valve list to count positioners, I/P converters, on off valves and purges.
2
Take Datasheet Bleed
Enter the steady air use of each device at the actual supply pressure.
3
Add Stroking Demand
Estimate air per stroke and how many strokes happen in a busy period.
4
Add Purges
Include bubblers, panel purges and analyzer needs.
5
Add Leakage
Allow for leaks in fittings and tubing, often 10 percent or as per the client standard.
6
Add Future Margin
Add the spare capacity your specification requires.
7
Size Equipment
Add dryer purge and select compressor, receiver and header.

Steps 1 to 4 give the real instrument air consumption, while steps 5 and 6 cover uncertainty and growth. Keep the margins visible in the sheet, so reviewers can see what is demand and what is allowance.

Quick Tip

Ask valve vendors for steady state air consumption at your actual supply pressure, not at their test pressure. Bleed rises with supply pressure, so a figure quoted at 1.4 bar can understate use at 4 bar.

Demand Formula and Worked Example

Q steady = N1 × q1 + N2 × q2
Q design = Q steady × (1 + leak ÷ 100) × (1 + margin ÷ 100)
Q compressor = Q design ÷ (1 minus purge ÷ 100)

Example:
40 positioners × 1.2 Nm³/h = 48 Nm³/h
20 on off valves × 0.5 Nm³/h average = 10 Nm³/h
Q steady = 58 Nm³/h
Q design = 58 × 1.10 × 1.20 = 76.6 Nm³/h
Q compressor = 76.6 ÷ 0.85 = 90.1 Nm³/h

Here 0.5 Nm³/h is an assumed average stroking demand per on off valve over a busy hour, and 15 percent is an assumed desiccant dryer purge. Replace both with your own datasheet values.

Instrument Air Consumption Calculator

Plant Instrument Air Demand
Result
Design demand 76.6 Nm³/h, compressor 90.1 Nm³/h
Advertisement

Second Worked Example: Air Used per Valve Stroke

An on off ball valve has a double acting actuator with a swept volume of 5 litres, supplied at 6 bar gauge. The free air per stroke is 5 × (6 + 1.013) ÷ 1.013 = 34.6 litres, about 0.035 Nm³.

If the valve cycles 10 times in an hour, it uses about 0.35 Nm³/h on average, but the peak during each stroke is much higher. Bullough notes a minimum of 0.0012 m³ (73 cubic inches) per operation for a spring less ball valve actuator, and the actuator styles are compared in valve actuator types.

Do You Know?

A spring return actuator uses air only to compress the spring, while a double acting actuator fills one side on every stroke in each direction. Choosing the actuator style and fail position therefore changes the instrument air consumption of a batch plant.

Sizing the Air Receiver

V = Q × t × Pa ÷ (P1 minus P2)
Q in Nm³/min, t in minutes, pressures in bar

Example:
Q = 76.6 ÷ 60 = 1.28 Nm³/min, t = 5 min
P1 = 7 bar g, P2 = 4.5 bar g, Pa = 1.013 bar
V = 1.28 × 5 × 1.013 ÷ 2.5 = 2.6 m³

The receiver holds enough air to let valves reach their safe position or let a standby compressor start after a trip. The hold up time t comes from the project or client standard, and the minimum pressure P2 is the lowest supply at which every fail safe valve still works.

Header and Distribution Sizing

CompressorDelivers free air at about 7 to 8 bar
ReceiverBuffers peaks and gives hold up
Dryer and FiltersMeet ISA 7.0.01 quality
Main HeaderLoop or ring with low pressure drop
Sub HeadersIsolation valve at each branch
Air Filter RegulatorSets supply at each instrument

Bullough recommends a typical plant air pressure around 6 bar, rarely above 8 bar, and his example header came out at 80 mm, so a 3 inch pipe was selected. Use the method in calculate pressure drop in pipes to keep the drop across the farthest branch small at peak flow.

A ring main feeds each consumer from two directions and keeps pressure steadier than a dead end line. Instrument branches usually end in a pneumatic manifold or individual filter regulators near the valves.

Quick Tip

Fit a pressure transmitter at the far end of the header, not only at the compressor. It shows the true pressure the valves see and gives an early alarm before positioners starve.

Myth: Steady bleed is the whole demand.
Fact: Stroking peaks can be many times the bleed and must be covered by the receiver and header.
Myth: A bigger compressor removes the need for a receiver.
Fact: The receiver supplies peaks and hold up time when a compressor trips.
Myth: Leaks are too small to matter.
Fact: Many small fitting leaks add up and can rival the instrument air consumption of many valves.
Myth: Any dry air is good enough.
Fact: ISA 7.0.01 also limits particles, oil and corrosive gases.

Instrument Air System Review Checklist

  • Every positioner, I/P converter and on off valve is counted from the latest index.
  • Bleed values are taken at the actual supply pressure.
  • Stroking demand of large and frequently cycling valves is included.
  • Leakage and future margins are stated separately.
  • Dryer purge loss is added to compressor capacity.
  • Receiver hold up time meets the project standard.
  • Header pressure drop is checked at peak flow.
  • Dew point, particle and oil limits match ISA 7.0.01.

Compressors themselves are covered in single stage and multi stage compressors, and a valve that hunts or chatters can burn air steadily, as shown in control valve troubleshooting. Partial stroke tests on ESD valves, described in partial stroke testing, also draw short bursts of air.

Advantages of a Careful Air Demand Estimate
  • Right sized compressor and dryer with lower energy use.
  • Stable header pressure during upsets.
  • Valves reach safe positions after a compressor trip.
  • Clear record for future plant expansion.
Limitations of the Estimate
  • Stroking demand depends on how the plant is operated.
  • Datasheet bleed varies with supply pressure.
  • Leakage grows with age and is hard to predict.
  • Margins can oversize equipment if stacked carelessly.
Advertisement

Ways to Reduce Air Use

Low Bleed Positioners
Replace old high bleed relays with low bleed digital units.
Leak Surveys
Use ultrasonic detectors and fix fittings on a schedule.
Right Supply Pressure
Set regulators no higher than the actuator needs.
Dryer Control
Use dew point dependent purge control on desiccant dryers.
Isolate Idle Units
Close air to shut down sections and spare panels.

Even a few low bleed retrofits can free compressor capacity for new valves, which is cheaper than adding a machine. For the valve side of such projects, see control valve sizing requirements.

Instrument Air Piping Design Paper

PDF
Piping Design of Instrument Air Distribution Systems
Bruce D. Bullough, Sebesta Blomberg, consumption data and header sizing examples

Instrument Air Compressor Video

Instrument Air Consumption FAQ

What is instrument air consumption?

It is the total flow of clean, dry compressed air used by all pneumatic instruments and actuators in a plant. Instrument air consumption is normally stated in Nm³/h or scfm at reference conditions.

It covers positioner bleed, converters, valve stroking, purges and leaks. This total then sets the size of the compressor, dryer, receiver and header for the plant.

How much air does a positioner use?

Bullough quotes one positioner at 1.21 Nm³/h at steady state, rising to 21.4 Nm³/h while moving. Modern low bleed digital positioners can use far less than older relay designs.

Always take the figure from the datasheet at your real supply pressure for the instrument air consumption sheet. Bleed rises as supply pressure goes up, so test pressure values can mislead.

Why is stroking demand important?

Each stroke fills the actuator volume with air at supply pressure in a few seconds. During a plant upset many valves move together and the flow peaks sharply.

The receiver and header must cover that peak without dropping below the minimum pressure. Steady bleed alone hides this short but heavy demand on the air system.

What does ISA 7.0.01 require?

It sets a pressure dew point at least 10 °C below the lowest ambient, and never above 4 °C at line pressure in any case. It also limits particles to 40 micrometres in the air stream.

Total oil content must stay below 1 ppm by weight, and the air must be free of corrosive or toxic gases. Many plants specify a dew point of minus 40 °C for extra safety.

How is the air receiver sized?

Use V = Q × t × Pa ÷ (P1 minus P2) with flow in Nm³/min and time in minutes. P1 is the normal pressure and P2 the lowest pressure at which valves still work.

For 1.28 Nm³/min, 5 minutes and a 2.5 bar drop, the receiver needs about 2.6 cubic metres of volume. The hold up time itself comes from the project standard.

Should dryer purge be added to the demand?

Yes, because a desiccant dryer uses part of the dried air to regenerate its beds. Power Engineering puts this purge at about 15 to 20 percent of compressor capacity.

Divide the design demand by one minus the purge fraction to get the compressor size. Dew point dependent purge control can reduce this loss a great deal.

How much margin should be added?

Most projects add a leakage allowance and a separate future margin to the instrument air consumption. Typical values come from the client standard, such as 10 percent leakage and 20 percent growth.

Keep each margin visible in the sheet rather than hiding it inside bleed values. Stacked hidden margins often lead to oversized compressors that waste energy.

Advertisement

Related Articles

External References

What We Learn Today

  • Instrument air consumption adds positioner and I/P bleed, valve stroking demand and purges, then applies leakage and future margins before sizing equipment.
  • A positioner may bleed about 1.2 Nm³/h at rest yet use over 20 Nm³/h while moving, so peaks must be covered by the receiver.
  • ISA 7.0.01 limits dew point to 4 °C at line pressure, particles to 40 micrometres and oil to 1 ppm in instrument air.
I hope you like above blog. There is no cost associated in sharing the article in your social media. Thanks for reading!! Happy Learning!!

Leave a Reply

Your email address will not be published. Required fields are marked *