Earth Fault Loop Impedance: 5 Vital Checks for Safe Tripping

Share:
Electrical Safety & Standards
Earth Fault Loop Impedance: 5 Vital Checks for Safe Tripping

A breaker can only protect people if enough fault current flows to trip it fast, and the loop impedance decides that current.

Ze and Zs BS 7671 Disconnection Time Loop Testing

When a live conductor touches earthed metal, fault current flows around a loop through the supply, the fault and the earth path. The lower the impedance of this loop, the faster the protective device trips.

Hello everyone, today we are going to learn what earth fault loop impedance means, how Ze and Zs are measured, and how to check that a circuit breaker will disconnect a fault within the required time.
earth fault loop impedance

What Is Earth Fault Loop Impedance?

Earth fault loop impedance is the total impedance of the path that fault current takes from the point of fault, through the protective conductor and earth return, back through the supply transformer and the line conductor. It is measured in ohms and written as Zs for a complete circuit.

The path depends on the earthing arrangement, explained in our TN, TT and IT earthing systems guide. In TN systems the return is metallic, so the loop is low and breakers can clear faults.

Loop tester connected at a socket to measure the fault loop of a final circuit
Image credit: SparkyFacts

Megger explains that the test proves enough fault current will flow to operate the protective device within the BS 7671 disconnection time. If the loop is too high, exposed metal can stay live at a dangerous touch voltage.

Two values matter. Ze is the external loop outside the installation, and Zs is the whole loop seen at the far end of a circuit.

Ze, Zs and the Loop Formula

Zs = Ze + (R1 + R2)
Fault current If = (Cmin × U0) ÷ Zs
Max Zs = (Cmin × U0) ÷ Ia

R1 = line conductor resistance, R2 = protective conductor resistance, Cmin = 0.95, U0 = 230 V, Ia = current for instant trip

Worked example, Type B 32 A MCB:
Ia = 5 × 32 = 160 A
Max Zs = 0.95 × 230 ÷ 160 = 1.37 Ω
Ze = 0.35 Ω, R1 + R2 = 0.52 Ω, Zs = 0.87 Ω
If ≈ 251 A, well above 160 A, so the breaker trips instantly

Typical declared Ze values are 0.35 Ω for TN C S supplies and 0.8 Ω for TN S supplies. Always measure the real value on site rather than relying on the declared one.

The same loop decides the prospective fault current, which links this test to short circuit fault current calculations.

5 Vital Checks for Safe Disconnection

1
Measure Ze
At the origin, with the main earth temporarily disconnected under safe isolation.
2
Measure R1 + R2
Continuity test from the board to the far point of each circuit.
3
Calculate or Measure Zs
Add Ze and R1 + R2, or test live at the furthest point.
4
Compare With Tables
Use BS 7671 Tables 41.2 to 41.4 for the device and time.
5
Apply the 80 Percent Rule
Measured Zs should be below 80 percent of the table value.

The 80 percent rule allows for conductor temperature rise during a fault, which increases resistance. A cold measurement of 1.37 Ω would fail, while 1.10 Ω or less passes for a Type B 32 A breaker.

Record every reading on the schedule of test results, including the device type and rating. This makes periodic inspection much faster.

Maximum Zs by Breaker Curve

DeviceInstant Trip CurrentMax Zs, 32 A80 Percent Value
Type B MCB5 × In1.37 Ω1.10 Ω
Type C MCB10 × In0.68 Ω0.55 Ω
Type D MCB20 × In0.34 Ω0.27 Ω

Type C and D curves need much lower loop values, which is why they suit motor circuits with short cable runs. Our MCB vs MCCB vs ELCB vs RCCB guide compares device choices.

Selecting the right rating comes first, as covered in MCB rating calculation. Coordination between devices is explained in breaker time current curves.

Test Methods and Safety

Safe IsolationProve dead before Ze testing
Two Wire TestHigh current, fast, may trip RCDs
Three Wire No TripLow current, avoids RCD tripping
Record ResultNote device and reading
Reconnect EarthNever leave the main earth off

Megger warns that no trip test modes can read slightly high, an effect known as RCD uplift. Where readings are close to the limit, repeat the test or use the calculated value.

Live testing exposes the tester to shock and arc hazards, so follow NFPA 70E electrical safety practice and wear suitable PPE.

How to Lower a High Loop Reading

Larger CPC
Increase the protective conductor size.
Shorter Cable Route
Reduce R1 + R2 by moving the board closer.
Change the Curve
Use Type B instead of Type C where loads allow.
Add an RCD
Provides fault protection when Zs is too high.
Tighten Terminations
Loose joints raise loop impedance.
Improve Supply Earth
Ask the utility to check a high Ze.

Protective conductor sizing is covered in the earth conductor size calculation article. Longer circuits also need a voltage drop calculation.

Breaker Check Calculator

Zs, Fault Current and Pass Check
Result
Zs 0.87 ohm, fault current 251 A, limit 1.10 ohm, PASS

This check covers 230 V TN circuits with 0.4 second disconnection. Always confirm against the tables in the current edition of BS 7671.

Good Practice
  • Measure, do not assume Ze.
  • Apply the 80 percent rule.
  • Record device type with each reading.
  • Retest after any alteration.
Common Errors
  • Leaving the main earth disconnected.
  • Ignoring RCD uplift.
  • Using Type C tables for Type B devices.
  • Testing without safe isolation.

Electrotechnik Loop Impedance PDF

PDF
Understanding Earth Fault Loop Impedance
Electrotechnik guide to loop paths, testing and maximum values

Loop Testing Explained Video

Loop Impedance FAQ

What is earth fault loop impedance?
The total impedance of the fault current path through the supply, line conductor and earth return.
What is Ze?
The external loop impedance outside the installation.
How is Zs calculated?
Zs equals Ze plus R1 plus R2.
What is the 80 percent rule?
Measured Zs should not exceed 80 percent of the table value.
What is the max Zs for a Type B 32 A MCB?
About 1.37 Ω, or 1.10 Ω after the 80 percent rule.
Why do readings vary with RCDs?
No trip test modes can read slightly high.
What if Zs is too high?
Increase the CPC, shorten the route, change the curve or add an RCD.

Related Articles

External References

What We Learn Today

  • Zs equals Ze plus the circuit R1 + R2 and sets the fault current.
  • Compare measured Zs with 80 percent of the BS 7671 table value.
  • Test safely and fix high readings before energising.
I hope you like above blog. There is no cost associated in sharing the article in your social media. Thanks for reading!! Happy Learning!!

Leave a Reply

Your email address will not be published. Required fields are marked *