Fail Safe Valve Position: Fail-Open vs Fail-Closed vs Fail-Locked

Share:
Process Instrumentation
Fail Safe Valve Position: Fail Open vs Fail Closed vs Fail Locked

A fail-safe valve position is the position a control valve moves to when it loses its control signal, instrument air, or actuator power.

This is a deliberate engineering decision — not a default. It is based on what is safest for the process and personnel when something goes wrong.

Selecting the wrong fail-safe valve position is a process safety error.

It cannot be corrected in the field without changing the actuator spring or valve action, a significant rework requiring a management of change.

FC / FO / FL Designation ATC vs ATO Action Spring Return vs Lock SIL and SIS Design

The fail safe valve position is determined by the process hazard, not by instrumentation convenience.

A cooling water valve should fail open. A fuel gas valve should fail closed. A fail-safe valve positioned incorrectly makes the process less safe when the instrument fails.

fail safe valve

What Is a Fail Safe Valve Position?

Hello! Today we are covering fail safe valve positions: fail-open, fail-closed, and fail-locked. These are defined during the process hazard analysis (PHA) stage of a project and documented on the piping and instrumentation diagram (P&ID). Every control valve on a P&ID has one of these three designations — and it matters enormously for process safety.

A control valve actuator has a preferred direction of travel when air or electrical signal is lost.

For a pneumatic spring-return actuator, the spring pushes the valve to its fail safe position.

For an electric actuator, the position is set by a spring return or a battery-backed drive that moves the valve on power loss. This is the fail-safe valve position.

Did You Know? The terms "air-to-close" (ATC) and "air-to-open" (ATO) refer to the actuator action, not the fail-safe valve position directly.

An ATC actuator closes the valve when air pressure is applied (and opens when air is lost). So an ATC valve is fail-open.

An ATO actuator opens the valve when air pressure is applied (and closes when air is lost). So an ATO valve is fail-closed.

On a P&ID, the fail-safe position is shown by the valve symbol: FC (fail closed), FO (fail open), or FL (fail locked). These annotations are definitive. The ATC/ATO notation describes the actuator mechanism that achieves that position.
FO
Fail-Open: valve goes to full open on loss of signal or air. Also marked as ATC (Air-To-Close) on actuator.
FC
Fail-Closed: valve goes to full closed on loss of signal or air. Also marked as ATO (Air-To-Open) on actuator.
FL
Fail-Locked: valve stays at its last position on loss of signal. Requires a lock-up relay or volume booster to maintain position.
PHA
Process Hazard Analysis: the study that determines which fail-safe position is correct for each valve in the plant.
Advertisement

The Three Fail Safe Valve Positions Explained

FO — Fail-Open
Fail-Open Valve

A fail-open valve moves to the fully open position when the control signal, instrument air, or actuator power is lost.

The spring in a spring-return pneumatic actuator pushes the valve open. The valve closes against this spring force during normal operation.

This is an ATC (Air-To-Close) actuator. Increasing air pressure closes the valve. Removing air pressure allows the spring to open it.

When to use fail-open: Any service where continued flow is safer than stopping flow on instrument failure.

Classic fail-open services: cooling water lines, steam heating on freeze-sensitive pipelines, and feed valves where stopping flow is more hazardous than continued flow.

Tip: A cooling water valve on a reactor or heat exchanger is almost always specified fail-open.

If the instrument air supply fails, the valve opens fully — providing maximum cooling to protect the process from overtemperature.

The alternative (fail-closed on a cooling water line) would stop cooling on instrument failure, allowing the process temperature to rise unchecked — exactly the scenario the cooling system was designed to prevent.
Did You Know? The fail-open position requires a spring that can overcome the full dynamic and static fluid forces acting on the plug at the design pressure differential.

For high-pressure valves, the spring force needed to open the valve against line pressure can be very large — requiring a large-bore actuator cylinder.

This is why fail-open high-pressure valves are often bigger and heavier than the equivalent fail-closed valve at the same pipe size and Cv. The spring has to do more work.
FC — Fail-Closed
Fail-Closed Valve

A fail-closed valve moves to the fully closed position on loss of control signal, instrument air, or actuator power.

The spring pushes the valve closed. The valve opens against this spring force during normal operation.

This is an ATO (Air-To-Open) actuator. Increasing air pressure opens the valve. Removing air pressure allows the spring to close it.

When to use fail-closed: Any service where stopping flow is safer than allowing uncontrolled flow on instrument failure.

Classic fail-closed services: fuel gas valves (stop fuel on loss of control), chemical injection valves, and high-pressure letdown valves that must close to prevent downstream overpressure.

Tip: A fuel gas valve feeding a burner is virtually always fail-closed.

If the flame goes out and the fuel control valve fails open, unburned gas accumulates in the firebox — creating an explosion hazard.

The fail-closed position shuts off fuel on loss of signal, giving the flame safeguard system time to respond. See the process control valves guide and the valve selection guide for how this integrates into burner management.
Did You Know? For a Safety Instrumented System (SIS) final element, the fail-closed valve must be proof-tested periodically to verify that it actually closes when the solenoid valve de-energises.

A valve that is fail-closed by design but whose spring has relaxed, whose actuator seals have hardened, or whose plug is stuck on sediment may not close when commanded.

IEC 61511 (see the control valve troubleshooting guide) requires periodic proof testing of all SIS final elements, including the full stroke test (or partial stroke test with statistical adjustment) of each fail-safe valve in the safety instrumented function.
Advertisement
FL — Fail-Locked
Fail-Locked Valve

A fail-locked valve stays at whatever position it held at the moment of signal loss.

It is neither fully open nor fully closed. It locks at its last position, also called fail-last or fail-in-place.

This is not achieved by a spring. A lock-up relay on the actuator air supply traps the air already in the cylinder when instrument air pressure drops below a threshold.

The trapped air holds the valve at its current position until the air supply is restored.

When to use fail-locked: Processes where both full-open and full-closed positions are unacceptable on failure. Moving to either extreme would cause more harm than staying at the current position.

Classic fail-locked services: large pipeline isolation valves (water hammer risk), temperature-critical processes where a sudden flow step damages equipment, and ratio control valves where an abrupt position change upsets the blend.

Tip: A fail-locked valve is not a substitute for a properly specified fail-open or fail-closed valve in a safety-critical application.

A lock-up relay can leak slowly over time, allowing the valve to drift from its last position after a long instrument air outage. This means a fail-locked valve is not a reliable safety function — it is a process continuity function.

For SIS applications, only fail-open or fail-closed positions are acceptable for the safety function. Fail-locked valves may be used for the regulatory control layer but must never be the SIS final element.
Did You Know? A fail-locked position is sometimes called "fail-last" or "fail-in-place" in instrument engineering documents.

On a P&ID, it may be annotated as FL, FLP (fail-last position), or FI (fail-in-place), depending on the company's documentation standard.

Always verify which abbreviation your project's P&ID legend uses before interpreting valve failure annotations. FL on one company's P&ID means fail-locked; on another's it may mean fail-low (fail to minimum position) — a completely different action.

How the Actuator Achieves Each Fail Safe Position

The fail-safe position is determined by the actuator type and its spring arrangement not by the valve body or trim alone.

Actuator TypeFail-Open (FO)Fail-Closed (FC)Fail-Locked (FL)
Pneumatic spring-return diaphragmSpring extends stem upward, opening valve (direct-acting body) or closing plug on seat (reverse action). Air pressure opposes spring.Spring pushes stem downward, seating plug. Air pressure lifts plug against spring.Not applicable — spring always drives valve to one end. Fail-locked requires a lock-up relay added to the air supply line.
Pneumatic piston actuatorSpring on one side of piston drives stem to open position. Double-acting variant uses a separate compressed air reservoir.Spring on other side of piston drives stem to closed. Air pressure to the cylinder opposes spring during normal operation.Lock-up relay traps air on both sides of piston on air supply loss. Valve holds last position.
Electric actuator (EIM, Auma, Rotork)Battery-backed motor drives to full open on power loss. Or spring-return mechanism within the actuator body.Battery-backed motor drives to full close on power loss. Spring-return option also available.Motor de-energises on power loss; mechanical brake holds last position. No battery needed.
Solenoid valve (on-off safety function)Normally open (NO) solenoid — spring holds open, energised to close. De-energises to open on power loss.Normally closed (NC) solenoid — spring holds closed, energised to open. De-energises to close on power loss.Latching solenoid — maintains last position without power. Not commonly used in SIS applications.
Never rely on the positioner or the DCS output to achieve a fail-safe position. The positioner is a control device, not a safety device. If instrument air is lost, the positioner cannot hold any position. The fail-safe position must be achieved by a physical mechanism in the actuator itself, independent of the positioner and control system.
Advertisement

Fail-Safe Valve Position Selector Tool

Fail-Safe Position Recommender
Select process conditions to get a recommended fail-safe valve position
-
-

Watch: Fail-Open, Fail-Closed and Fail-Lock Control Valve Explained

Fail Safe Valve Position Questions

What does FC mean on a control valve?
FC means fail-closed: the valve moves to fully closed on loss of signal or air. This is an ATO (Air-To-Open) actuator — air pressure opens it, and the spring closes it on air loss.
What is the difference between ATC and ATO actuators?
ATC (Air-To-Close) closes the valve when air is applied and opens when air is removed, giving a fail-open (FO) valve. ATO (Air-To-Open) opens when air is applied and closes when removed, giving a fail-closed (FC) valve.
When is fail-locked (FL) the correct choice?
Fail-locked is a process continuity choice used when both full-open and full-close are unacceptable. It must never be an SIS final element — IEC 61511 requires a defined safe position (open or closed) for every safety function.
How is the fail-safe position determined during a project?
The fail-safe position is determined during the Process Hazard Analysis (PHA) or HAZOP study. The team evaluates what is safer for the process at each failure extreme, then documents FC, FO, or FL on the P&ID.
Can the fail-safe position be changed in the field?
Not without changing the actuator spring or repiping the air connections. The positioner cannot change the fail position. The spring must be replaced and actuator action reversed through a formal management of change process.

External References

Advertisement

What We Learn Today

  • FC (fail-closed) uses an ATO actuator: spring closes the valve on air loss. FO (fail-open) uses an ATC actuator: spring opens the valve on air loss. FL (fail-locked) uses a lock-up relay to trap air and hold the last position.
  • The fail-safe position is determined by process hazard analysis, not by instrumentation convenience. A cooling water valve is FO. A fuel gas valve is FC. Both positions have specific safety reasons behind them.
  • Fail-locked valves are a process continuity choice, not a safety choice. They must never be the final element in a Safety Instrumented System (SIS) — IEC 61511 requires a defined safe position (open or closed).
“The fail-safe valve position is the most important thing on the P&ID that no one looks at during normal operation — and the only thing that matters when the instrument fails.”

Leave a Reply

Your email address will not be published. Required fields are marked *