Motor Control Center (MCC) Explained

Share:
Industrial Electrical Systems
Motor Control Center (MCC) Explained

Nearly every pump, fan, and compressor motor in a plant traces back to a single steel enclosure full of starters and breakers, and understanding how this lineup is built is essential for anyone maintaining that equipment.

Motor Control Center MCC Buckets Motor Starters Switchgear

A motor control center is a modular steel enclosure that groups multiple motor starter units, called buckets, into one assembly fed from a common incoming bus, simplifying both wiring and maintenance for dozens of motors at once.

Hello everyone, today we are going to look closely at this equipment lineup, its buckets, its bus structure, and why plants standardize on this single enclosure instead of scattering individual starters across a facility.

This builds on motor starting methods and motor protection relays, both of which live inside the buckets described here.
Motor Control Center

What Is a Motor Control Center

A motor control center is an assembly of one or more enclosed vertical sections, each holding a common power bus and a set of removable or fixed compartments called buckets.

Every bucket contains the components needed to start, run, and protect one motor, typically a contactor, an overload relay, fuses or a circuit breaker, and sometimes a small controller or VFD.

Incoming power arrives at a single main breaker, feeds a vertical bus running the height of each section, and distributes down to every bucket connected to that section.

Why Plants Standardize on This Design

Grouping dozens of motor starters into a single lineup means one incoming feed, one set of protective devices to coordinate, and one physical location for operators and technicians to check during a fault.

Without this consolidation, each motor would need its own separate enclosure, feeder cable, and disconnect, multiplying both installation cost and the number of places a fault could originate.

Advertisement

Anatomy of a Bucket

Contactor
Switches motor power on and off in response to a control signal
Overload Relay
Trips the circuit if sustained current exceeds the motor's rating
Fuses or Breaker
Provides short circuit protection ahead of the contactor
Control Wiring
Connects start, stop, and status signals back to the control system
Bucket TypeTypical UseKey Component
Full voltage non reversingSimple pumps and fansSingle contactor
Full voltage reversingConveyors, valve actuatorsTwo interlocked contactors
Reduced voltage starterLarge motors needing soft startingStar delta or soft starter module
Variable frequency driveMotors needing speed controlIntegrated VFD unit
Advertisement

Bus Structure and Power Distribution

A vertical bus runs the full height of each section, carrying power from the horizontal main bus at the top down to every bucket stacked in that column.

Bus bracing and short circuit ratings must match the maximum available fault current at the installation, since an undersized bus can fail catastrophically during a severe fault rather than simply tripping a breaker.

Grounding and Bonding Requirements

A continuous ground bus running the length of the lineup, bonded to every section's frame and to each bucket's chassis, gives fault current a low impedance path back to the source.

Without solid grounding, a fault inside one bucket can raise the enclosure to a dangerous touch voltage rather than tripping the protective device quickly, turning a contained fault into a serious shock hazard.

Main Breaker and Feeder Sizing

The main incoming breaker or fused switch must be sized for the sum of connected motor loads plus reasonable diversity, not simply added up worst case, since not every motor runs simultaneously at full load.

A poorly sized main device either nuisance trips under normal starting current or fails to protect the bus during an actual fault, so this calculation deserves careful attention during design.

Did You Know
Many modern lineups use intelligent buckets with built in communication, reporting motor current, run hours, and trip history directly to the plant SCADA system without separate wiring for each signal.
Advertisement

Selecting and Sizing a Lineup

1
List every motor to be served, its horsepower, and its starting method before laying out buckets.
2
Size the vertical and horizontal bus for available fault current, not just running load.
3
Leave spare bucket space for future motors rather than filling every section from day one.
4
Coordinate protective device settings across the lineup using time current curves so a downstream fault does not trip the main.

Draw Out vs Fixed Mounted Buckets

A draw out bucket can be racked out from its compartment while the vertical bus stays energized behind a safety shutter, letting a technician remove and replace a failed unit with minimal downtime.

A fixed mounted bucket is bolted permanently in place and wired directly, which costs less initially but requires the whole section to be de energized for any repair or replacement work.

Plants running continuous processes, where an unplanned motor outage is expensive, often justify the extra cost of draw out construction purely on the reduced repair time it offers.

Documenting the Lineup for Future Work

A single line diagram showing every section, bucket, and its connected motor, kept current as changes are made, saves enormous time during troubleshooting and future expansion planning.

Recording each protective device's actual settings alongside its coordination study results means a technician replacing a tripped relay years later can restore the exact same protection scheme without guesswork.

Ventilation, Heat, and Enclosure Ratings

Every contactor, overload relay, and VFD inside a bucket generates heat, and a lineup with too many high load buckets in a small room can quickly exceed its rated operating temperature.

Enclosure ratings such as NEMA 1 for indoor clean areas or NEMA 12 for dusty environments determine how much natural ventilation is even possible, which in turn affects how densely buckets can be packed.

Forced air cooling or a dedicated air conditioned electrical room becomes necessary once VFD content in a lineup grows large enough that passive ventilation alone cannot keep components within their rated temperature range.

Working With Reduced Voltage and VFD Buckets

A large motor started direct on line can draw six to eight times its rated current for a few seconds, stressing the bus and upstream transformer if too many start together.

Reduced voltage starters and VFD buckets limit this inrush, but they also take up more physical space and cost more per unit than a simple contactor and overload combination.

Warning
Never work inside an energized bucket without following lockout tagout procedures, the vertical bus behind the compartment remains live even when an individual bucket's breaker is open.

Motor Control Center vs Individual Starters

Centralized Lineup

One location, shared bus, easier coordination, but a single point of failure for many motors.

Individual Starters

Distributed risk and simpler single circuits, but far more wiring, space, and maintenance points.

Most industrial plants favor the centralized lineup for anything beyond a handful of motors, accepting the single point of failure in exchange for dramatically simpler installation and maintenance.

Routine Maintenance and Inspection

Thermal imaging surveys, usually conducted annually while the equipment is energized and under load, catch loose connections and overheating components long before they cause an unplanned trip.

Torque checking bus connections during a planned outage, using the manufacturer's specified values, prevents the loosening that thermal cycling naturally causes in bolted joints over years of operation.

Keeping a spare bucket of each common type on hand dramatically reduces downtime when a unit does eventually fail, since a spare can often be swapped in well under an hour.

Standards Governing Design and Installation

In North America, NEMA ICS 18 and UL 845 set construction and testing requirements for a motor control center, covering everything from bus bracing to bucket interlocking.

Internationally, IEC 61439 2 covers low voltage switchgear and controlgear assemblies more broadly, with specific provisions that a manufacturer must satisfy before labeling equipment compliant for a given fault current rating.

Specifying the correct standard early in a project avoids a costly mismatch discovered only after equipment has already been ordered and delivered to site.

Arc Flash Considerations

Every section of a modern lineup requires an arc flash hazard label showing the incident energy level, required personal protective equipment, and safe approach boundaries for anyone working nearby.

Calculating these values typically follows the IEEE 1584 methodology, factoring in available fault current, clearing time of upstream protective devices, and the physical working distance from the equipment.

Common Mistakes to Avoid

1
Undersizing the main bus for future motor additions, forcing a costly retrofit later.
2
Skipping protective device coordination studies, leading to nuisance trips of the main breaker.
3
Poor ventilation planning, letting heat from VFD buckets shorten the life of nearby components.
4
Ignoring arc flash labeling requirements on each section of the lineup.

Upgrading an Aging Lineup

A facility running decades old equipment often faces a choice between full replacement and a targeted retrofit that swaps only the most obsolete buckets while reusing the existing bus and enclosure.

Retrofit kits from several manufacturers allow a modern bucket, complete with electronic overload protection and communication capability, to be installed into an older frame without replacing the entire lineup.

This approach usually costs a fraction of full replacement while still delivering the improved protection and diagnostic visibility that a fully modern system provides.

Watch: How a Motor Control Center Works

Motor Control Center FAQs

What is a bucket in a motor control center?
A removable compartment holding one motor's contactor, overload relay, and protective device.
How is the main breaker sized?
Based on total connected load with reasonable diversity, plus available fault current at the site.
Can a bucket be replaced while the lineup is energized?
Only if it uses a draw out design and strict procedures, otherwise the section must be de energized.
What is the difference between an MCC and a switchboard?
A switchboard mainly distributes feeders, while this lineup specifically houses motor starting equipment.
Why do VFD buckets need extra ventilation?
Variable frequency drives generate significant heat that must be removed to avoid shortening component life.
How many motors can one lineup support?
It depends on bus rating and physical sections, ranging from a handful to several dozen motors.
Is intelligent monitoring required?
No, but it is increasingly common since it reduces wiring and gives early warning of motor problems.
What standard governs arc flash labeling?
NFPA 70E in North America sets the requirements for arc flash boundary calculation and labeling.

Related Articles on This Site

External References

Advertisement

What We Learn Today

  • This kind of lineup groups many motor starters into one enclosure fed from a shared bus.
  • Each bucket holds a contactor, overload relay, and protective device for one motor.
  • Bus sizing, protective coordination, and ventilation planning are the most common design pitfalls.
I hope you like above blog. There is no cost associated in sharing the article in your social media. Thanks for reading!! Happy Learning!!

Leave a Reply

Your email address will not be published. Required fields are marked *