VFD Braking Resistor: 5 Costly Sizing Mistakes to Avoid

Share:
Motors & Drives
VFD Braking Resistor: 5 Costly Sizing Mistakes to Avoid

When a motor slows faster than its load wants to, the energy has to go somewhere, and the resistor turns it into heat.

Dynamic Braking Brake Chopper DC Bus Overvoltage Resistor Sizing

A braking resistor lets a VFD stop a high inertia load quickly by burning regenerated energy as heat. Without it, the DC bus voltage rises and the drive trips on overvoltage.

Hello everyone, today we are going to understand how a VFD braking resistor works, why drives trip on overvoltage during deceleration, and how to size the resistor correctly.
braking resistor

What Is a VFD Braking Resistor?

A braking resistor is a power resistor connected to the DC bus of a VFD through a switching transistor called the brake chopper. It absorbs energy returned by the motor when it acts as a generator during deceleration.

When the drive lowers output frequency faster than the load can slow on its own, the rotor runs faster than the field. The motor then generates power back into the drive.

braking-resistor
Image credit: EEPower

A standard drive has a diode rectifier that cannot send energy back to the mains. The returned energy charges the DC bus capacitors and the voltage rises quickly.

If nothing absorbs it, the drive trips on DC bus overvoltage, one of the common VFD trip causes. The resistor solves this simply and cheaply.

How Dynamic Braking Works

Fast DecelerationFrequency drops faster than load speed
Motor RegeneratesMotor acts as a generator
DC Bus RisesCapacitors charge above normal
Chopper Switches OnTransistor connects the resistor
Heat DissipatedEnergy leaves as heat, bus returns to normal

The brake chopper is usually an IGBT controlled by the drive. It switches on above a set DC voltage and off when the voltage falls back.

For a 400 V class drive, the normal DC bus is around 540 to 560 V. The chopper typically switches on well above this level, so always check the threshold in the drive manual.

ABB Technical Guide No. 8 compares this method with regenerative braking, where an active front end returns energy to the supply instead of wasting it.

Braking Resistor Sizing Formulas

Maximum resistance R = Vdc² ÷ Peak braking power
Average power = Peak power × Braking time ÷ Cycle time

Worked example:
Chopper voltage Vdc = 700 V
Peak braking power = 15 kW
R max = 700² ÷ 15000 = 32.7 Ω
Choose R between the drive minimum and 32.7 Ω
Braking 10 s every 60 s, duty = 16.7 percent
Average power = 15 × 0.167 ≈ 2.5 kW continuous rating

The resistance must never be lower than the minimum value stated by the drive maker. A lower value draws too much current through the chopper transistor and can destroy it.

Peak braking power comes from the load inertia and the required stopping time. Kinetic energy equals half the inertia multiplied by the square of angular speed.

5 Costly Sizing Mistakes to Avoid

1
Resistance Too Low
Overloads the chopper transistor beyond its current rating.
2
Power Rating Too Small
Resistor overheats on repeated stops.
3
Ignoring Duty Cycle
Cranes and hoists brake far more often than fans.
4
No Thermal Protection
A failed chopper can leave the resistor energized and on fire.
5
Poor Mounting
Resistors inside panels overheat nearby components.

Mistake 4 is a real fire risk. Fit a thermal switch or overload on the resistor and wire it to stop the drive or open the supply.

Configure the drive braking parameters correctly too, as described in VFD parameter configuration. Enable the chopper and set resistor protection values.

Braking Methods Compared

MethodEnergy UseCostBest For
Coast to stopNo brakingNoneFans, low inertia loads
DC injectionHeat in motorLowHolding at standstill
Dynamic braking resistorHeat in resistorLow to mediumOccasional fast stops
Regenerative front endReturned to supplyHighFrequent braking, lifts, cranes
Common DC busShared between drivesMediumMulti drive lines

For frequent heavy braking, regenerative drives often pay back through energy savings. For occasional stops, a braking resistor is the simplest answer.

DC injection braking heats the motor itself, so it should be used only for short periods at low speed.

Where Dynamic Braking Is Needed

Cranes and Hoists
Lowering loads regenerate continuously.
Centrifuges
Very high inertia with fast stop requirements.
Conveyors
Downhill conveyors regenerate energy.
Large Fans
Fast stops for maintenance or process safety.
Test Rigs
Controlled deceleration cycles.
Machine Tools
Rapid spindle stops.

Overhauling loads like hoists and downhill conveyors regenerate while running, not only while stopping. Their resistors need much higher continuous ratings.

Motor slip turns negative during regeneration, a concept covered in induction motor slip.

Dynamic Braking Sizing Calculator

Resistance and Power Rating
Sizing result
R max 32.7 ohms, average power 2.50 kW

Always check that the chosen value is above the drive minimum resistance. Then pick a standard resistor with power rating above the average power.

Advantages
  • Simple and low cost.
  • Fast stopping of high inertia loads.
  • Prevents DC bus overvoltage trips.
  • Works with standard drives.
Drawbacks
  • Wastes energy as heat.
  • Needs space and ventilation.
  • Fire risk without thermal protection.
  • Not ideal for continuous regeneration.

ABB Electrical Braking Guide PDF

PDF
Technical Guide No. 8, Electrical Braking
ABB drives guide comparing resistor, flux and regenerative braking

Braking Resistor Wiring Video

Braking Resistor FAQ

What does a braking resistor do?
It burns regenerated energy as heat so the drive does not trip on overvoltage.
What is a brake chopper?
A transistor that connects the resistor when DC bus voltage is high.
Can the resistance be too low?
Yes, it can overload and destroy the chopper transistor.
How is power rating chosen?
From peak braking power multiplied by the braking duty cycle.
Is regenerative braking better?
It saves energy but costs more, so it suits frequent braking.
Why does the drive trip on overvoltage?
Regenerated energy charges the DC bus capacitors.
Does a fan need a braking resistor?
Only if it must stop faster than it would coast.

Related Articles

External References

What We Learn Today

  • Regenerated energy raises the DC bus, and the chopper sends it to the resistor.
  • Resistance must stay above the drive minimum and power must suit the duty cycle.
  • Thermal protection and good mounting prevent overheating and fire.
I hope you like above blog. There is no cost associated in sharing the article in your social media. Thanks for reading!! Happy Learning!!

Leave a Reply

Your email address will not be published. Required fields are marked *