Safety and SIS · Glossary

What is Safety Integrity Level?

Symbol: SILSIL 1 to SIL 4Safety and SIS

Safety integrity level is a target level of risk reduction for a safety instrumented function, from SIL 1 (lowest) to SIL 4.

Advertisement

Safety Integrity Level Explained

SIL is set during hazard and risk analysis, for example with LOPA. The SIF must then meet the PFDavg range, the architectural constraints and the systematic requirements for that SIL.

Most process SIFs are SIL 1 or SIL 2; SIL 3 is less common and SIL 4 is rare in process plants.

Safety Integrity Level: Typical Values

SIL 1PFDavg 10⁻² to 10⁻¹, RRF 10 to 100
SIL 2PFDavg 10⁻³ to 10⁻², RRF 100 to 1000
SIL 3PFDavg 10⁻⁴ to 10⁻³, RRF 1000 to 10,000
SIL 4PFDavg 10⁻⁵ to 10⁻⁴
Advertisement

Calculators for Safety Integrity Level

Free Downloads

Frequently Asked Questions

What is Safety Integrity Level?

Safety integrity level is a target level of risk reduction for a safety instrumented function, from SIL 1 (lowest) to SIL 4.

Is a SIL 2 transmitter enough for SIL 2?

No. The whole SIF, including logic and valve, must meet SIL 2; a certified device only helps.

What does SIL capable mean?

The device has been assessed as suitable for use up to that SIL within the stated limits.