What is an Orifice Plate?
An orifice plate is a thin plate with a precise bore clamped in a pipe; the DP across it is used to calculate flow.
Orifice Plate Explained
The orifice plate is the most widely used flow element. It is cheap, has no moving parts and is fully covered by ISO 5167-2, so it can be used without flow calibration.
Pressure is taken through flange, corner or D and D/2 taps. Accuracy depends on a sharp upstream edge, correct straight runs and clean impulse lines.
Orifice Plate Formula
| qm | mass flow (kg/s) |
| C | discharge coefficient |
| ε | expansibility factor |
| d | bore (m) |
| Δp | differential pressure (Pa) |
| ρ₁ | upstream density (kg/m³) |
Calculators for Orifice Plate
Free Downloads
Frequently Asked Questions
What is an Orifice Plate?
An orifice plate is a thin plate with a precise bore clamped in a pipe; the DP across it is used to calculate flow.
Which way does an orifice plate face?
The sharp square edge faces upstream. The bevel, if any, is downstream. The tab is usually marked with the inlet side.
What is the difference between a flow orifice and a restriction orifice?
A flow orifice measures flow from DP. A restriction orifice only limits flow or drops pressure and is not used for measurement.
Learn more on the blog
Mistakes in DP flow measurement
A practical guide on instrumentationblog.in with more detail on orifice plate and how it is applied on real plants.
Read Full ArticleRelated Terms
More Flow Measurement Terms
All flow measurement terms · Full glossary A to Z