Control Valve · Comparison

Linear vs Equal Percentage

Side by side comparison: how they work, where each fits, and which to choose.

Quick answer: Use linear where the valve takes most of the system pressure drop; use equal percentage where the valve drop falls as flow rises, which is most process loops.

Advertisement

Linear vs Equal Percentage: Comparison Table

AspectLinearEqual Percentage
Inherent curveCv proportional to travelEqual % change of Cv per travel
Best whenValve ΔP nearly constantValve ΔP falls with flow
Typical loopsLevel, some pressure loopsFlow, temperature, most pressure loops
At low authorityBehaves like quick openingBecomes near linear installed
Advertisement

Choose Linear when

  • High valve authority systems

Choose Equal Percentage when

  • Pumped systems with large pipe and equipment losses

Key Differences Explained

What matters is the installed characteristic: flow against travel in the real system. Aim for a nearly linear installed curve so loop gain stays steady.

When in doubt, equal percentage is the safer default for process control.

Advertisement

Related Glossary Terms

Free Calculators

Free Downloads

Frequently Asked Questions

What is the difference between Linear and Equal Percentage?

Use linear where the valve takes most of the system pressure drop; use equal percentage where the valve drop falls as flow rises, which is most process loops.

Can the positioner change the characteristic?

Yes, with a characterising curve, but resolution at low travel still comes from the trim.

What is quick opening for?

On off and relief duty.

How do I check?

Calculate flow at several openings with the system curve.